Troubleshooting and Maintenance
6-12 | CFW-11W G2
6
ATTENTION!
Electronic boards have components sensitive to electrostatic discharges.
Do not touch the components or connectors directly. If necessary, first touch the grounded metallic
frame or wear a ground strap.
Do not execute any applied potential test on the inverter!
If necessary, contact WEG.
When installed in proper environment and operating conditions, the inverters require little maintenance.
presents the main procedures and time intervals for preventive maintenance.
contains the recommended inspections to be performed every 6 months after the start-up.
Table 6.3:
Preventive maintenance
Maintenance
Interval
Instructions
HMI battery replacement
Every 10 years
See
Cleaning the cooling system and changing
the coolant
Every 5 years
Contact WEG
Monthly inspection
Once a month
Open the panel and check for leaks. If
present, it must be corrected
Refill 1.5 % of Inhibitor CorteC VpCI-649
Once a year
Contact WEG
The following refrigeration system parameters must be registered annually:
Measure the ethylene glycol concentration using a refractometer. If the concentration is below the recommended
level, ethylene glycol must be replaced in the system.
Measure the pH of the solution. The pH of the solution should be between 8.2 ... 10. If the pH is outside this
range, a complete fluid change must be made.
Table 6.4:
Periodic inspections every six months
Component
Anomalies
Corrective Action
Terminals, connectors
Loose Screws
Tighten
Loose Connectors
Printed circuit boards
Buildup of dust, oil, moisture, etc.
Cleaning
Smell
Replace
Power module/Power connections
Buildup of dust, oil, moisture, etc.
Cleaning
Loose connection screws
Tighten
Power resistors
Discoloration
Replace
Smell
6.5.1 Cleaning Instructions
When it is necessary to clean the inverter, follow the instructions below:
Electronic boards:
1. Disconnect the power supply of the inverter and wait for 10 minutes.
2. Remove the dust accumulated on the boards using an anti-static brush or ion compressed air gun (Example:
Charges Burtes Ion Gun (non-nuclear) reference A6030-6DESCO).
3. If necessary, remove the boards from the inverter.
4. Always wear a grounding strap.