www.weg.net
ABW - Air Circuit Breaker | 15
1.6 TECHNICAL DATA
Circuit breaker
ABW08 ABW16 ABW20 ABW25 ABW32 ABW40 ABW50
ABW63
Standard
IEC 60947-2
Maximum rated current (40 °C) - In max. (A)
800
1,600
2,000
2,500
3,200
4,000
5,000
6,300
Current setting
(0.4 ~1.0) x In max
Rated operational voltage - Ue (V)
690
Rated insulation voltage - Ui (V)
1,000
Impulse voltage - Uimp (kV)
12
Frequency (Hz)
50 / 60
Number of poles
3
Versions
Fixed - withdrawable
Protection units
LSIG Electronics
Rated ultimate short-circuit
breaking capacity - Icu (kA)
220 / 380 / 415 V
65
85
100
120
440 / 480 / 500 V
65
85
100
120
600 / 690 V
50
85
85
100
Rated service short-circuit
breaking capacity - Ics (kA)
220 / 380 / 415 V
65
85
100
120
440 / 480 / 500 V
65
85
100
120
600 / 690 V
50
85
85
100
Rated short-time withstand current
- Icw (kA)
1s
50
85
85
100
2s
42
75
75
90
3s
36
65
65
85
Rated making capacity
- Icm (kA peak)
220 / 380 / 415 V
143
187
220
264
440 / 480 / 500 V
143
187
220
264
600 / 690 V
105
187
187
220
Utilization categories
B
Operating time (ms)
Opening (max.)
40
Closing (max.)
80
Mechanical lifespan
(number of operations)
Without maintenance
20,000
15,000
10,000
10,000
With maintenance
1)
30,000
20,000
15,000
15,000
Electrical lifespan
(number of operations)
Without maintenance
5,000
5,000
2,000
2,000
With maintenance
1)
10,000
10,000
5,000
5,000
Altitude (m)
≤2,000
2)
Ambient temperature
Operation
-5...40 °C
3)
Storage
-20...60 °C
Weight (kg)
4)
Withdrawable
61
85
143
184
Fixed
32
42
74
101
Connection terminals -
withdrawable/fixed
Horizontal
Standard
Standard
Standard
Standard
Vertical
Optional
Optional
Optional
Optional
External dimensions
H x W x D (mm)
Withdrawable
430 x 334 x 375
430 x 412 x 375
430 x 629 x 375
430 x 785 x 375
Fixed
300 x 300 x 295
300 x 378 x 295
300 x 597 x 295
300 x 751 x 295
Notes: 1) According to the maintenance routines indicated in the manual.
2) For installation above 2,000 m from sea level, please consider the voltage and current derating factors, as shown in the chart below.
3) For ambient temperature above 40 °C, check maximum rated current values in the chart below.
4) It may vary according to the configuration of optional accessories.
Table 1.5: Technical data
Summary of Contents for ABW Series
Page 2: ......
Page 3: ...User Manual Series ABW Air Circuit Breaker Language English...
Page 4: ......
Page 7: ......
Page 56: ......
Page 57: ...Manual del Usuario S rie ABW Interruptor Abierto Idioma Espa ol...
Page 58: ......
Page 61: ......
Page 110: ......
Page 111: ...Manual do Usu rio S rie ABW Disjuntor Aberto Idioma Portugu s...
Page 112: ......
Page 115: ......
Page 160: ...160 ABW Disjuntor Aberto www weg net 6 5 PR ALARME Figura 6 5 Pr alarme...