10 | ABW - Air Circuit Breaker
1.2 SERVICE CONDITIONS
1.2.1 Ambient temperature
Operation:
-5...40 ºC, with an average of 24h of up to 35 ºC. In order to apply the ABW circuit breakers with
a temperature above 40 °C, consider the maximum values of nominal current presented in the table below:
Circuit
breaker
Maximum
current @
40 ºC (A)
Terminals
of circuit
breaker
(mm)
Recom-
mended
bars
(mm)
Nominal current (A)
Terminals of position
Horizontal
Vertical
Ambient temperature
Ambient temperature
40 ºC
45 ºC
50 ºC
55 ºC
60 ºC
40 ºC
45 ºC
50 ºC
55 ºC
60 ºC
ABW06D..
630
50x15
50x10
630
630
630
630
630
630
630
630
630
630
ABW08D..
800
800
800
800
800
800
800
800
800
800
800
ABW10D..
1,000
(2x)
50x10
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
ABW13D..
1,250
1,250
1,250
1,250
1,250
1,250
1,250
1,250
1,250
1,250
1,250
ABW16D..
1,600
1,600
1,600
1,600
1,550
1,550
1,600
1,600
1,600
1,600
1,550
ABW20E..
2,000
75x20
(2x)
80x10
2,000
2,000
2,000
2,000
2,000
2,000
2,000
2,000
2,000
2,000
ABW25E..
2,500
(3x)
80x10
2,500
2,500
2,500
2,400
2,300
2,500
2,500
2,500
2,450
2,350
ABW32E..
3,200
(4x)
80x10
3,200
3,200
3,100
3,000
2,900
3,200
3,200
3,150
3,050
2,950
ABW40E..
4,000
(3x)
100x10
(4x)
100x10
4,000
4,000
3,900
3,800
3,650
-
-
-
-
-
.
(2x)
125x15
(3x)
120x10
-
-
-
-
-
4,000
4,000
3,950
3,900
3,850
ABW50F.
5,000
(2x)
125x20
(4x)
120x10
5,000
5,000
4,900
4,800
4,700
5,000
5,000
4,950
4,850
4,750
ABW63G.
6,300
(2x)
150x20
(4x)
160x10
6,300
6,300
6,200
6,100
6,000
6,300
6,300
6,250
6,150
6,050
Table 1.1:
Storage:
-20...60 ºC.
1.2.2 Altitude of installation
≤ 2,000 m. In order to apply the ABW circuit breakers in altitudes above 2,000 m, apply the nominal current and
voltage reduction factors presented in the table below.
Altitude (m)
2,000
3,000
4,000
5,000
Insulation voltage (V)
1,000
900
700
600
Maximum operational voltage (V)
690
590
520
460
Current correction factor
1 x In
0.99 x In
0.96 x In
0.94 x In
Table 1.2:
Summary of Contents for ABW Series
Page 2: ......
Page 3: ...User Manual Series ABW Air Circuit Breaker Language English...
Page 4: ......
Page 7: ......
Page 56: ......
Page 57: ...Manual del Usuario S rie ABW Interruptor Abierto Idioma Espa ol...
Page 58: ......
Page 61: ......
Page 110: ......
Page 111: ...Manual do Usu rio S rie ABW Disjuntor Aberto Idioma Portugu s...
Page 112: ......
Page 115: ......
Page 160: ...160 ABW Disjuntor Aberto www weg net 6 5 PR ALARME Figura 6 5 Pr alarme...