ON and the sensor reverts to the automatic-on mode.
• Once the sensor returns to automatic-on mode, either the switch or occupancy
detection can turn the load ON.
Override: Switch 2
To override all sensor functions, set DIP switch 2 to the ON position. The green LED
comes on and stays on for the duration of the override.
This bypasses the occupancy detection control functions of the sensor, but still
allows the lights to be manually controlled with a light switch, if one is installed.
Time Delay: Switches 3, 4, 5
The sensor will hold the lights on as long as occupancy is detected. The time delay
countdown starts when no motion is detected. After no motion is detected for the
length of the time delay, the sensor will turn the lights off. The sensor can select the
time delay using SmartSet, or you can select a fixed time delay.
• SmartSet records occupancy patterns and uses this history to choose an optimal
time delay from 5 to 30 minutes. SmartSet behavior starts immediately and is
refined continually as history is collected.
Walk-through mode turns the lights off three minutes after the area is initially
occupied, if no motion is detected after the first 30 seconds. If motion continues
beyond the first 30 seconds, the selected time delay applies.
LED: Switch 6
When enabled, the green Ultrasonic Activity LED on the sensor will light when the
sensor detects motion.