SENSOR ADJUSTMENT
The sensors are factory preset to allow for quick installation in most applications.
Verification of proper wiring or coverage, or customizing the sensor’s settings can
be done using the following procedures. To make adjustments, open the Front Cover
with a small screwdriver.
Before making
adjustments, make
sure the office
furniture is installed,
lighting circuits are
turned on, and the
HVAC systems are in
the overridden/ on
position. VAV systems
should be set to their
highest airflow. Set
the Time Delay to the
desired settings. See
“DIP Switch Setting”,
next page.
To Test Occupancy Sensors
1. Ensure the Ultrasonic Activity LED is enabled (DIP switch 6 ON).
2. Ensure the Time Delay is set for
Test Mode*
using the “5 seconds/SmartSet”
setting. (DIP switches 3, 4, & 5 are OFF).
3. Ensure that the Ultrasonic Sensitivity trimpot is set to about 90%, clockwise.
4. Remain still. The LED should not flash. The lights should turn off after 5 seconds.
(If not, see “Troubleshooting.”)
5. Move about the coverage area. The lights should come on. Adjust the Ultrasonic
Sensitivity as necessary to provide the desired coverage (Green LED indicates
activation from the ultrasonic sensor).
When testing and adjustment is complete, reset DIP Switches to the desired
settings, and replace the cover on the sensor.
* Test Mode
is a temporary state that starts when you first set the sensor’s DIP
switches for the “5 sec/SmartSet mode” (switches 3, 4, 5 OFF). If you need to
invoke the
Test Mode
and the DIP switches are already set for 5 sec/SmartSet,
toggle DIP switch 5 ON then back to the OFF position. This provides a 5 minute
test period. During the test period, the Time Delay is only 5 seconds.