Technical Data
WiFi Snow Melting Control 670
Boiler & Mixing / Electric
Literature
670_A, 670_C, 670_D, 670_J, 670_U
Control
Microprocessor control. This is not a safety (limit) control.
Packaged weight
4.3 lb. (1960 g)
Dimensions
6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm)
Display
3.5", color touchscreen
Enclosure
Blue PVC plastic, NEMA type 1
Approvals
CSA C US, meets class B: ICES & FCC Part 15
Ambient conditions
-4 to 122°F (-20 to 50°C), < 90% RH non-condensing, outdoor use permitted when used in NEMA 3 enclosure
Power supply
115 V (ac) ±10%, 60 Hz, 20 VA
Relays
230 V (ac), 5 A, 1/3 hp
Boiler modulating output
0-10 V (dc) 500 Ω min impedance / 4-20 mA 1 kΩ max impedance
Injection mixing pump
230 V (ac), 2.4 A 1/6 hp, fuse T2.5 A 250V
Floating mixing output
230 V (ac), 5 A
Analog mixing output
0-10 V (dc) 500 Ω min impedance / 4-20 mA 1 kΩ max impedance
Manual melt call
Short or 0 - 32 V(ac)
Communications
WiFi 802.11n, 2.4 GHz, WPA2 encryption
Mobile app
Apple iOS 12 or higher, Android 8 or higher
Sensors
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
–Included
Outdoor Sensor 070 and 2 of Universal Sensor 082
–Optional
tekmar type: 072, 073, 082, 090, 094, 095