17 of 48
System Status Menu
Description
Range
Access
MANUAL MELT INPUT
When Manual Melt wiring terminal 13 is shorted to common wiring terminal 14, the control is enabled
and enters the melting operation unless prevented by warm weather shut down or cold weather
cut out. When the manual melt input is disconnected, the control completes the melting cycle and
then returns to off, idle or storm operation.
Conditions: Always
Off, Enabled
User
Installer
TEKMARNET
When tekmarNet communication is present, the status shows active. When there is no tekmarNet
communication, the status is off.
Conditions: Always
Off, Active
User
Installer
BOILER TARGET
The boiler target calculated by the control based on outdoor temperature, slab temperature and the
melting, idling, or storm setpoints. “- - -” is displayed when no heat is required.
Conditions: Application mode is set to Boiler or Mix.
– – –,
50 to 230°F
(10.0 to 110.0°C)
User
Installer
BOILER SUPPLY
Current boiler supply water temperature.
Conditions: Application mode is set to Boiler or Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
BOILER OUTPUT
Current boiler plant percent output.
Conditions: Application mode is set to Boiler or Mix.
0 to 100%
User
Installer
STAGE 1
Current status of the stage 1 relay.
Conditions: Application mode is set to PWM Zone, Mixing, Boiler, or Mix.
On or Off
User
Installer
STAGE 2
Current status of the stage 2 relay.
Conditions:
Boiler type is set to Stage 2.
On or Off
User
Installer
MIX TARGET
The mix target calculated by the control based on outdoor temperature, slab temperature
and one of either the melting, idling, or storm setpoints. ”- - -” is displayed when no heat is
required.
Conditions: Application mode is set to Mixing or Mix.
– – –,
70 to 200°F
(21.0 to 93.5°C)
User
Installer
MIX SUPPLY
Current mix supply water temperature.
Conditions: Application mode is not set to Electric.
-31 to 266°F
(-35.0 to 130.0°C)
User
Installer
MIX OUTPUT
Current position of the mixing valve or output of the variable speed injection pump.
Conditions: Application mode is set to Mixing or Mix.
0 to 100%
User
Installer
SYSTEM PUMP
Current status of the system loop pump.
Conditions: Application mode is set to PWM Zone, Mixing, Boiler or Mix.
On or Off
User
Installer
HEAT RELAY
Current status of the heat relay.
Conditions: Application mode is set to Electric, PWM Zone, Mixing.
On or Off
User
Installer
ELECTRIC ENABLE RELAY
Current status of the electric snow melt enable relay.
Conditions: Application mode is set to Electric.
On or Off
User
Installer