Monitor Menu
Description
Range
Access
MELTING ENERGY
Records the amount of energy since the counter was last reset.
Conditions: Available when Application Mode is set to Electric.
0 to 999999 kWh
User
Installer
MELTING HOURS
Records the number of melting hours since the counter was last reset.
Conditions: Always available.
0 to 999999
hours
User
Installer
HEAT HOURS
Records the number of hours the boiler fired or the electric cable heated since the counter
was last reset.
Conditions: Available when Application Mode is Boiler, Mix and Electric.
0 to 999999
hours
User
Installer
HEAT CYCLES
Records the number of cycles the boiler turned on or the electric cable heated since the
counter was last reset.
Conditions: Available when Application Mode is Boiler, Mix and Electric.
0 to 999999
cycles
Installer
SYSTEM PUMP
Records the number of hours the system pump has operated since the counter was last
reset.
Conditions: Available when Application Mode is not set to Electric.
0 to 999999
hours
Installer
SLAB SENSOR HIGH
Records the highest measured slab temperature since the counter was last reset.
Conditions: Available when Snow/Ice Sensor is set to In-slab or Slab Sensor = On.
-58 to 167°F
(-50.0 to 75.0°C)
Installer
SLAB SENSOR LOW
Records the lowest measured slab temperature since the counter was last reset.
Conditions: Available when Snow/Ice Sensor is set to In-slab or Slab Sensor = On.
-58 to 167°F
(-50.0 to 75.0°C)
Installer
OUTDOOR HIGH
Records the highest measured outdoor air temperature since the counter was last reset.
Conditions: Always available.
-67 to 149°F
(-55.0 to 65.0°C)
Installer
OUTDOOR LOW
Records the lowest measured outdoor air temperature since the counter was last reset.
Conditions: Always available.
-67 to 149°F
(-55.0 to 65.0°C)
Installer
BOILER HIGH
Records the highest measured boiler temperature since the counter was last reset.
Conditions: Available when Application Mode is set to Boiler or Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
BOILER LOW
Records the lowest measured boiler temperature since the counter was last reset.
Conditions: Available when Application Mode is set to Boiler or Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
MIX SUPPLY HIGH
Records the highest measured mix temperature since the counter was last reset.
Conditions: Available when Application Mode is set to PWM Zone, Mixing or Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
MIX SUPPLY LOW
Records the lowest measured mix temperature since the counter was last reset.
Conditions: Available when Application Mode is set to PWM Zone, Mixing or Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
RESET ALL?
Resets all the counters in the monitor menu at once.
Conditions: Always available.
N/A
Installer