20 of 48
Description
Range
Access
MELTING SETPOINT
Select the desired temperature of the snow melt surface when melting.
Conditions: Always available.
32 to 95°F
(0.0 to 35.0°C)
Default = 36°F
(2.0°C)
User
Installer
IDLING SETPOINT
Select the desired temperature of the snow melt surface when idling. Idling preheats the slab
when the slab is dry but cold and allows faster reaction time to reach the melting temperature
when snow is detected. Recommended for commercial use only.
Conditions: Always available.
OFF, 20 to 95°F
(-6.5 to 35.0°C)
Default = Off
User
Installer
STORM SETPOINT
Select the desired temperature of the snow melt surface while operating in the storm
operation. Storm operation temporarily preheats the slab to allow faster reaction time to
reach the melting temperature when snow is detected. Storm operation is automatically
activated by the Internet weather forecast or manually started by a User Switch or Gateway.
Conditions: Always available.
OFF, 20 to 95°F
(-6.5 to 35.0°C)
Default = Off
User
Installer
MANUAL MELT TIME
Select the amount of running time when manually starting the system.
Conditions: Always available.
0:30 to 24:00
hours
Default = 4:00
hours
User
Installer
ADD MELT TIME
Select the amount of additional melting time after the Snow/Ice Sensor is dry. This allows
low spots on the slab to fully dry before the snow melting system is shut off.
Conditions: Snow/ice sensor is set to In-slab.
0:00 to 6:00
hours
Default = 0:00
hours
Installer
STORM RUN TIME
Select the amount of storm run time to pre-heat the slab when advised of a winter storm
warning.
Conditions:
Storm setpoint is set to a temperature.
0:30 to 24:00
hours
Default = 8:00
hours
Installer
SENSITIVITY
Select how sensitive Snow/Ice Sensor is to water detection.
Conditions: Snow/ice sensor is set to In-slab or Aerial.
Auto, Min, -2, -1,
Mid, +1, +2, Max
Default = Auto
Installer
WWSD
Select the temperature above which the snow melting system is shut off during warm
weather. This allows the snow or ice to melt off the slab naturally.
Conditions: Always available.
Auto, 32 to 95°F
(0.0 to 35.0°C)
Default = Auto
Installer
CWCO
Select the temperature below which the snow melting system is shut off during extremely
cold weather. Below this temperature, the heat loss of the slab exceeds the capacity of the
boiler or heating appliance.
Conditions: Always available.
Off, -30 to 50°F
(-34.5 to 10.0°C)
Default = 10°F
(-12.0°C)
Installer