All these water chemistry requirements are corresponding to 
the average parameters of the water delivered usually, please 
contact your water supplier or local autorities in order to confirm 
the compliance.

Notice

* Systems using OneFlow

®

 technology are effective at control-

ling limescale formation inside the plumbing system at influ-
ent hardness levels up to 427mg per liter (28.8°D, 51.3°F) of  
calcium carbonate. Due to variances in water chemistry, 
427mg per liter is a recommended hardness maximum due 
to potential aesthetic issues related to soft scale residue 
formation outside the plumbing system. Testing should be 
performed to determine proper application where hardness 
levels exceed 427mg per liter.
** Just as with conventional water softening media, OneFlow

® 

media needs to be protected from excess levels of certain met-
als that can easily coat the active surface, reducing its effective-
ness over time. Public water supplies rarely, if ever, present a 
problem, but if the water supply is from a private well, confirm 
that the levels of iron (Fe) and manganese (Mn) are less than 0.3 
mg/l and 0.05 mg/l, respectively.

Notice

† OneFlow

®

 media does not reduce silica scaling. While silica 

tends to have a less significant effect on scale formation than 
other minerals, it can act as a binder that makes water spots 
and scale residue outside the plumbing system difficult to 
remove. This 20 mg/l limitation is for aesthetic purposes.
†† All other water contaminants must meet the requirements of 
the local water control agency of each specific country where 
OneFlow

®

 is sold and installed. Specific Mineral and Metal 

Maximum Contaminants Level’s, identified in the above Feed 
Water Chemistry Requirements list, supersedes those require-
ments. Water known to have heavy loads of dirt and debris may 
require a pre-filtration prior to OneFlow

®

.

2.1      Feed Water Chemistry Requirements

pH

6.5-8.5

Hardness (maximum)

427 mg/l CaCO3 (28,8°dH, 51,3°fH)*

Water Pressure

1.03 - 6.2 bar

Temperature

5 - 38°C

Free Chlorine

<2 mg/l

Iron (maximum)

0.3 mg/l**

Manganese (maximum)

0.05 mg/l**

Copper

1.3 mg/l

Oil & H2S

Must be Removed

Total Phosphates

< 3.0 mg/l

Silica (maximum)

20 mg/l

TDS

1500 mg/l

††

3. Installation

3.1      Installation Precautions

You are required to consult the local and state building and 
plumbing codes and regulations prior to installation. If the 
information in this manual is not consistent with local building 
or plumbing codes, the local codes should be followed. Inquire 
with governing authorities for additional local requirements.
Periodic inspection and yearly maintenance by a licensed 
contractor is required. Corrosive water conditions and/or 
unauthorized adjustments or repair could render OneFlow

® 

ineffective for service intended. Regular checking and cleaning 
of the device’s internal components helps assure maximum 
life and proper product function. Frequency of cleaning and 
inspection depends upon local water conditions.
• 

Do not use with water that is microbiologically unsafe or 
of unknown quality without adequate disinfection before 
or after the system

• 

Connect system ONLY to COLD water supply. Water 
temperature cannot exceed 38°C. Do NOT install system 
on HOT water line. Failure to limit line temperature to 
38°C may result in housing failure and damage.

• 

Do NOT allow system to freeze. Turn off water supply to 
housing and drain housing if temperature falls below 5°C.

• 

Please provide a shut-off valve before and after the 
OneFlow

®

 device so it can be isolated for maintenance 

at all times.

• 

Do NOT install system in direct sunlight or where system 
is exposed to harsh chemicals or may be subjected to 
being struck by moving equipment, carts, mops or any 
other item that may cause damage.

• 

Do NOT mount the OneFlow system near any source of 
heat or above any device or area that would be adversely 
effected by water.

• 

Do NOT install system with pressure above 6.2 bar.

• 

Do NOT install the system backwards with the feed water 
line connected to the outlet. The direction of flow through 
the OneFlow unit is always Through the inlet first; keep 
this in mind when determining installation location. 

• 

The device should be installed in an upright and level 
position, with both inlet and outlet connections in a hori-
zontal position.

• 

We do not recommend to apply any other antiscalants 
before or after OneFlow.

• 

Do NOT use liquid pipe compounds for fitting connec-
tions 3/4”MBSP. Use two to three wraps of PTFE tape.

SOFT SCALE SPOTTING

Depending on hardness of the water, soft scale spotting 
may occur on external plumbing surface. But in most 
cases, these spots can be easily wiped down with a 
damp cloth and will not form hard scale deposits.

Summary of Contents for OneFlow OFTWH-R

Page 1: ...Watts Oneflow com OneFlow OFTWH R OFTWH Innovative Scale Control Installation manual Installation and Operation Manual UK OFTWH R OFTWH...

Page 2: ...lure to read and follow all safety and use information can result in serious personal injury property damage or damage to the equipment This manual contains important operation maintenance and precaut...

Page 3: ...ment salt free without additional chemicals Improves efficiency of all water heating devices and down stream plumbing components Simple sizing installation standard 3 4 connections Perfect solution fo...

Page 4: ...ts pH 6 5 8 5 Hardness maximum 427 mg l CaCO3 28 8 dH 51 3 fH Water Pressure 1 03 6 2 bar Temperature 5 38 C Free Chlorine 2 mg l Iron maximum 0 3 mg l Manganese maximum 0 05 mg l Copper 1 3 mg l Oil...

Page 5: ...proper product function Frequency of cleaning and inspection depends upon local water conditions 3 2 Installation instructions 1 Close the water system Turn off all equipment to be fed by the OneFlow...

Page 6: ...certifications and may compromise equipment protection water quality and equipment life Cartridge replacement procedure 1 IMPORTANT All other equipment connected to the OneFlow system must be turned...

Page 7: ...rior notice Warranty All sales and contracts for sale are expressly conditioned on the buyer s assent to Watts terms and conditions found on its website at www wattswater eu Watts hereby objects to an...

Page 8: ...ax 49 0 6341 9656 560 www wattswater de Belgium The Netherlands Luxemburg Watts Benelux Beernemsteenweg 77A 8750 Wingene Belgium tel 32 51658708 fax 32 51658720 www wattswater eu Denmark Sweden Finlan...

Reviews: