Lync WQ-SF
SECTION 3: Operation
L- OMM-004_A
•
2/23/2022
Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
22
of
54
Remote Lock
The controller does not allow the unit/system to go into Regeneration until the Regeneration
Lockout Input signal to the unit is cleared. This requires a contact closure to activate the unit.
The recommended gauge wire is 16 AWG with a maximum wire length run of 50 feet.
Regeneration Day Override Feature
If the Day Override option is turned on and the valve reaches the set Regeneration Day
Override value, the Regeneration Cycle starts if no other unit is in Regeneration. If other units
are in regeneration, it is added to a regeneration queue. This occurs regardless of the remaining
volume available.
Lock Settings (access to Master Programming)
Lock Settings prevents the user from accessing Master Programming. In Master Programming,
select the desired Lock Settings option (Off, Time Based, Delayed, or Enter Code).
•
Time Based
- User must set clock to 12:01 pm to unlock
•
Delayed
- User must press and hold the
Left
and
Down
buttons for 60 continuous
seconds to unlock
•
Enter Code
- User must input code "1201" to unlock
Flow Meter Equipped Controller
As treated water is used, the Volume Remaining display counts down from the calculated
system capacity to zero. When zero is reached, a Regeneration Cycle begins if no other units
are in regeneration.
Capacitive Buttons
Capacitive button entry warrant different consideration than tactile button entry. Do not wear
gloves. Be sure to keep your hands and the capacitive buttons free of debris, grease, or water.
Buttons may become temporarily unresponsive if environmental conditions change such as
sudden humidity or temperature changes. If buttons become unresponsive, wait 5 to 10 minutes
for the buttons to recalibrate.
LED Status indicator
•
Blue - Unit in Service
•
Flashing Blue - Regeneration Queued
•
Green - Regeneration
•
Flashing Green - Standby
•
Red - Error with codes
Power Loss Backup
Time of day super capacitor backup for power loss; rated to last minimum 12 hours