background image

Installation Guidelines 

• Consult local codes for requirements and restrictions applicable

to the area. FEBCO recommends at least 20 psi (138 kPa) for

system supply pressure.

• Install the valve only in the orientation/flow direction shown. The air

inlet operates in the vertical position. Installation in any other manner

causes the device to malfunction.

• Install the valve where it is accessible for periodic testing, mainte­

nance, and repair. The clearances recommended apply to exterior

and interior installations. (See Figures 1 and 2.) These minimums

do not apply to removable protective enclosures. Refer to local

codes for requirements in the area.

• Before installing the valve into the supply line, flush the line of all

foreign material.

Failure to flush the line may cause the check valves to become 

fouled and require disassembly for cleaning. Install the device 

where spillage is not objectionable, as instantaneous siphon 

conditions and pressure surges can cause spitting. 

• When threading the assembly in line, place the wrench only on

the ball valve hex ends. Keep pipe dope (sealant) off the interior

surfaces of the valve. After installation, fill the assembly with water

and test the device to ensure proper operation. Open the inlet ball

valve to pressurize the unit. Slowly open the outlet ball valve to fill

the downstream line.

Maintain the downstream pressure above 5 psi (34 kPa) to keep 

the spring-loaded air inlet poppet closed. If the check valve fails to 

hold 10 psi minimum, it has become fouled and must be cleaned. 

Close both ball valves and bleed pressure from the device before 

disassembly. (For more information, see “Service Procedure.”) 

All assemblies are tested at the factory for proper operation and 

leakage. If the valve does not pass the field test, it may contain 

a fouled check valve. This condition is not covered by the fac­

tory warranty. Remove the valve cover then inspect and clean 

the check seats. Any damage or improper operation caused by 

pipeline debris or improper installation/startup is not included in 

the factory warranty. In case of a warranty claim, contact the local 

supplier or FEBCO representative. Do not remove the assembly 

from the pipeline. 

• Protect the assembly from freezing and excessive pressure increases.

Pressure increases can be caused by thermal expansion or water

hammer. Eliminate excessive pressure situations to protect the valve

and system from possible damage. Use the plastic test cock plugs

and tethers included in the packaging, if required. For information on

freeze protection, download IS-F-765-Winterization.

Figure 1 Top View 

3" Minimum 

3" Minimum 

FIgure 2 Side View 

12" Minimum Above the 

Highest Outlet or Water Level

FLOW

Summary of Contents for FEBCO 765

Page 1: ...eze event and cannot prevent a freeze event from occurring User action is required to prevent freeze conditions from causing product and or property damage FEBCO Series 765 Pressure Vacuum Breakers ar...

Page 2: ...valve to pressurize the unit Slowly open the outlet ball valve to fill the downstream line Maintain the downstream pressure above 5 psi 34 kPa to keep the spring loaded air inlet poppet closed If the...

Page 3: ...m breaker 6 Slowly open test cock No 2 while watching the poppet in the air inlet The poppet must unseat If the air inlet does not open it is sticking and must be repaired 7 Close test cock No 2 and r...

Page 4: ...sembly into the valve body Position the spring into the recessed area on the top side of the check assembly In some cases it may be easier to position the spring on the check assembly before positioni...

Page 5: ...6 1024564 1024564 6 O Ring 1101068 1101068 398 140 72 398 140 72 398 247 72 398 247 72 7 Spring 630 096 630 096 10 Stem 200 767 200 767 13 Retainer 300 096 300 096 300 088 300 088 14 Spring 630 108 6...

Page 6: ...in material and workmanship under normal usage for a period of one year from the date of original shipment In the event of such defects within the warranty period the Company will at its option replac...

Page 7: ...e les conditions de gel ne causent des dommages au produit et ou la propri t Les casse vides pression FEBCO de la s rie 765 sont utilis s pour la protection contre les conditions de siphonnement rebou...

Page 8: ...robinet bille de sortie pour remplir le conduit en aval AVIS Maintenez la pression en aval sup rieure 5 psi 34 kPa pour garder le clapet d entr e d air ressort ferm Si le clapet antiretour ne parvient...

Page 9: ...ment le robinet d essai n 2 tout en surveillant le clapet dans l entr e d air Le clapet doit se d gager Si l entr e d air ne s ouvre pas elle est bloqu e et doit tre r par e 7 Fermez le robinet d essa...

Page 10: ...emble de clapet dans le corps de vanne Positionnez le ressort dans la zone encastr e sur le c t sup rieur de l ensemble de clapet AVIS Dans certains cas il peut tre plus facile de positionner le resso...

Page 11: ...2 300 093 300 089 300 089 300 083 300 083 4 Boulon 6 1024564 1024564 6 Joint torique 1101068 1101068 398 140 72 398 140 72 398 247 72 398 247 72 7 Ressort 630 096 630 096 10 Tige 200 767 200 767 13 Ba...

Page 12: ...un indicateur du seuil de gel pour les ensembles de casse vide pression dans une configuration BMS IMS Garantie limit e FEBCO la Soci t garantit que chacun de ses produits est exempt de vice de mat ri...

Page 13: ...ocurra la congelaci n Se requiere la acci n del usuario para evitar que las condiciones de congelaci n causen da os al producto y o a la propiedad Los interruptores de presi n y vac o PVB FEBCO Serie...

Page 14: ...a v lvula de bola de salida para llenar la l nea corriente abajo AVISO Mantenga la presi n corriente abajo por encima de 5 psi 34 kPa para mantener cerrada la v lvula de asiento accionada por la v lvu...

Page 15: ...vac o 6 Abra lentamente el puerto de prueba No 2 mientras observa la v lvula de obturador en la entrada de aire La v lvula de obturador no debe estar asentada Si la entrada de aire no se abre se est...

Page 16: ...en el cuerpo de la v lvula Coloque el resorte en el rea empotrada en la parte superior del conjunto de retenci n AVISO En algunos casos puede ser m s f cil colocar el resorte en el conjunto de retenci...

Page 17: ...2 Dosel 300 092 300 093 300 089 300 089 300 083 300 083 4 Perno 6 1024564 1024564 6 Junta t rica 1101068 1101068 398 140 72 398 140 72 398 247 72 398 247 72 7 Resorte 630 096 630 096 10 V stago 200 7...

Page 18: ...ce este kit para agregar un indicador del umbral de congelaci n para los conjuntos de PVB en una configuraci n de BMS IMS Garant a limitada FEBCO la Empresa garantiza que todos los productos no presen...

Reviews: