AERCO ProtoNode FPC-N34 & FPC-N35 User Manual
CHAPTER 2 – BACnet/LonWorks Setup
OMM-0107_0B
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
13
of
108
GF-150
Ph.: 800-526-0288
03/07/2017
ProtoNode FPC-N34
S Bank DIP Switches
Profile
S0
S1
S2
S3
BACnet/IP
Off
Off
Off
Off
BACnet MS/TP
ON
Off
Off
Off
Metasys N2
Off
ON
Off
Off
Modbus TCP/IP or Modbus RTU
ON
ON
Off
Off
*Modbus to 8 WHM/BST Units
Off
Off
ON
Off
*BACnet to 8 WHM/BST Units
ON
Off
ON
Off
*Metasys N2 to 8 WHM/BST Units
Off
ON
ON
Off
ProtoNode FPC-N35
LonWorks
Off
Off
Off
Off
*Lon to 8 WHM/BST Units
ON
Off
Off
Off
Figure 2-5: S Bank DIP Switches
*NOTE:
For WHM or BST systems auto-discovery cannot be done. Be sure that the
S Bank DIP Switches are set properly.
2.4.2
Enabling Auto-Discovery (Not used on BST or WHM)
The S3 DIP switch is used to both enable Auto-Discovery of known devices attached to the
ProtoNode, and to save the recently discovered configuration.
•
See the table in Figure below for the switch setting to enable Auto-Discovery.
•
If the ProtoNode is being installed for the first time, set S3 to the
ON
position to enable
Auto-Discovery.
•
Cycle the power to the ProtoNode to start Auto-Discovery
•
The ON position is when the DIP switches are set closest to the inside of the box.
NOTE
: Allow 10 minutes for the Auto-Discovery process to complete.
•
After Auto-Discovery is complete, turn off S3 to save the configuration.
S3 DIP Switch Auto-Discovery Mode
S3
Auto-Discovery ON – Build New Configuration
ON
Auto-Discover OFF – Save Current Configuration
Off
Figure 2-6: S3 DIP Switch setting for Auto Discovering Devices
S0 S1 S2 S3
S0 – S3 DIP
Switches
S Bank DIP Switch Location
S0 S1 S2 S3