CHAPTER 2 – BACnet/LonWorks Setup
OMM-0107_0B
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
11
of
108
GF-150
Ph.: 800-526-0288
03/07/2017
CHAPTER 2.
BACnet/LonWorks Setup for ProtoNode
FPC-N34/FPC-N35
2.1 Record Identification Data
Each ProtoNode has a unique part number located on the side or the back of the unit. This
number should be recorded, as it may be required for technical support. The numbers are as
follows:
AERCO ProtoNode
Model
AERCO Part Number
Serial ProtoNode N34
64129
LonWorks ProtoNode N35
64130
Figure 2-1: ProtoNode Part Numbers
•
ProtoNode FPC-N34 units have the following 3 ports: RS-485, Ethernet, RS-485
•
ProtoNode FPC-N35 units have the following 3 ports: LonWorks, Ethernet, RS-485
2.2 Point Count Capacity and Registers per Device
The total number of Modbus Registers presented by all of the devices attached to the ProtoNode
cannot exceed:
Part number
Total Registers
FPC-N34-0645
1,500
FPC-N35-1051
1,500
Figure 2-2: Supported Point Count Capacity
Devices
Registers Per Device
Unit Address Range
AM Managing Boiler/Heater
95
Addr 1 to 16
AM Dependent Boiler/Heater
49
Addr 1 to 16
C-More BMK/INN
12
Addr 1 to 16
Modulex & Modulex EXT
10
Addr 1 to 8
ECS * IND/SP/DW
7
Addr 17 to 32
BMS/BMSII/ACS
51
Addr 128 to 228
BST/WHM
186 (for 1 up to 8 devices) Addr 1 to 8 on C-More (SSD address = 247)
*
Does not apply
to
Pneumatic or self-contained controls
Figure 2-3: Modbus Registers per Device