AERCO ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: Eight C-More Boilers/Heaters and BST/WHM Master
Page
74
of
108
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0107_0B
03/07/2017
Ph.: 800-526-0288
GF-150
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon
SNVT
Lon
Direction
Modbus
Address
8
Run Hours Upper
SMD_BAS_IP_HTR_08_[17]
AV:1017
Data Float
203
nvoHTR_08_18 inc count (9)
Output (non-polled)
31017
8
Run Hours Lower
SMD_BAS_IP_HTR_08_[18]
AV:1018
Data Float
204
nvoHTR_08_19
inc count (9)
Output (non-polled) 31018
8
Oxygen Level
SMD_BAS_IP_HTR_08_[19]
AV:1019
Data Float
205
nvoHTR_08_20
inc count (9)
Output (non-polled) 31019
Master Addr 247
Master Control Values
247
Write Cntrl Val to
BST/WHM
SMD_BAS_IP_Ctrl_[1]
* write "1" to
send Value to
WHM
AV:51
Data Float
2
nvoCtrl_2
inc count (9)
Input/Output
40051
247
BST/WHM Timeout
SMD_BAS_IP_Ctrl_[3]
**Read
Only**,
0=WHM
Present,
1=WHM
Absent
AV:53
Data Float
4
nvoCtrl_4
inc count (9)
Input/Output
40053
Read Master Operating Values
247
Mode
SMD_BAS_IP_OpVal_[0]
AV:100
Data Float
6
nvoOpVal_1
inc count (9)
Output (non-polled)
30100
247
Setpoint
SMD_BAS_IP_OpVal_[1]
AV:101
Data Float
7
nvoOpVal_2
inc count (9)
Output (non-polled)
30101
247
Setback Setpt
SMD_BAS_IP_OpVal_[2]
AV:102
Data Float
8
nvoOpVal_3
inc count (9)
Output (non-polled)
30102
247
Setback Start
SMD_BAS_IP_OpVal_[3]
AV:103
Data Float
9
nvoOpVal_4
inc count (9)
Output (non-polled)
30103
247
Setback End
SMD_BAS_IP_OpVal_[4]
AV:104
Data Float
10
nvoOpVal_5
inc count (9)
Output (non-polled)
30104
247
Auto Master
SMD_BAS_IP_OpVal_[5]
AV:105
Data Float
11
nvoOpVal_6
inc count (9)
Output (non-polled)
30105
247
Avg Outlet Temp
SMD_BAS_IP_OpVal_[6]
AV:106
Data Float
12
nvoOpVal_7
inc count (9)
Output (non-polled)
30106
247
Units Active
SMD_BAS_IP_OpVal_[7]
AV:107
Data Float
13
nvoOpVal_8
inc count (9)
Output (non-polled)
30107
247
Units Faulted
SMD_BAS_IP_OpVal_[8]
AV:108
Data Float
14
nvoOpVal_9
inc count (9)
Output (non-polled)
30108
247
Master Addr
SMD_BAS_IP_OpVal_[9]
AV:109
Data Float
15
nvoOpVal_10
inc count (9)
Output (non-polled)
30109
247
Header Temp
SMD_BAS_IP_OpVal_[10]
AV:110
Data Float
16
nvoOpVal_11
inc count (9)
Output (non-polled)
30110
247
Outdoor Temp
SMD_BAS_IP_OpVal_[11]
AV:111
Data Float
17
nvoOpVal_12
inc count (9)
Output (non-polled)
30111