Installation Guidelines 

Indoors 

For indoor installations, the assembly needs to be easily 

accessible to facilitate testing and servicing. If it is located in a 

line close to a wall, be sure the test cocks are easily accessible. 

A drain line and air gap should be piped from the relief valve 

connection as shown in Figure 1. This is where evidence 

of discharge is clearly visible, signaling the need to protect 

against water damage. Therefore, never install the assembly in 

concealed locations. (For more information, download the ES-

AG/EL/TC specification at watts.com.) 

Figure 1 

Air Gap 

Main 

Strainer 

Meter 

2

1

2

" – 3" 

12" Minimum 

Outside 

In an area where freezing conditions do not occur, the assembly 

can be installed outside. The most satisfactory installation is 

above ground; thus, the assembly should be installed in this 

manner. 
Backflow preventers should not be installed in pits unless 

approved by local codes. In such cases, a modified pit 

installation is preferred. 

NOTICE

 

In an area where freezing conditions can occur, the assembly 

should be installed above ground in an insulated enclosure, as 

shown in Figure 2. (For more information, download the ES-WB 

specification at watts.com.) 
The assembly must be installed in an accessible location to 

facilitate testing and servicing. A discharge line should be piped 

from the air gap at the relief valve connection to ensure there is 

adequate drainage. Never pipe the discharge line directly into a 

drainage ditch, sewer, or sump. Never install the assembly where 

any part of the unit could become submerged in standing water. 

Figure 2 

WattsBox 

12" Minimum 

Parallel 

Two or more smaller-sized assemblies can be piped in parallel 

(when approved) to serve a large supply pipe main, as shown in 

Figure 3. This type of installation is employed where increased 

capacity is needed beyond that provided by a single valve and 

permits testing or servicing of an individual valve without shutting 

down the complete line. 
The number of assemblies used in parallel should be determined 

by the engineer’s judgment based on the operating conditions of 

a specific installation. 
For parallel valve installations, the total capacity of the 

assemblies should equal or exceed that required by the system. 

2

1

2

" – 3" 

Figure 3 

Summary of Contents for 009 Series

Page 1: ...f the product s internal components helps assure maximum life and proper product function NOTICE For Australia and New Zealand line strainers should be installed between the upstream shutoff valve and...

Page 2: ...he assembly should be installed above ground in an insulated enclosure as shown in Figure 2 For more information download the ES WB specification at watts com The assembly must be installed in an acce...

Page 3: ...lear remove the first check valve and clean thoroughly NOTICE Periodic relief valve discharge may occur on dead end service applications such as boiler feed lines or cooling tower makeup lines due to...

Page 4: ...lder assembly 5 To reassemble the relief valve press the seat firmly into place in the body center the spring on the seat and insert the cover and relief valve module as a unit straight into the bore...

Page 5: ...ew assembly from the repair kit O rings should be cleaned or replaced as necessary and lightly greased with the FDA approved silicon grease 5 Reassemble the check valve modules Check modules are insta...

Page 6: ...n the relief valve of a new installation working with a BMS controller not included 88003057 FP RFK BF BMS CFS BMS Sensor Retrofit Connection Kit Series 009 LF009 LFU009 SS009 U009 Sizes to Includes f...

Page 7: ...of an existing installation working with cellular communication to send alerts by email message SMS text message or voice call 88003062 FP RFK BF CFS Cellular Sensor Retrofit Connection Kit Series 009...

Page 8: ...hich is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chem...

Page 9: ...e du produit et son bon fonctionnement AVIS En Australie et en Nouvelle Z lande les cr pines de conduite doivent tre install es entre le robinet d arr t en amont et l entr e du dispositif de pr ventio...

Page 10: ...nditions de gel peuvent se produire l ensemble doit tre install au dessus du sol dans une enceinte isol e conform ment la figure 2 Pour plus d informations t l chargez la sp cification ES WB l adresse...

Page 11: ...iodique de la soupape de d charge peut se produire dans les applications de service aux extr mit s telles que les conduites d alimentation des chaudi res ou les conduites d appoint des tours de refroi...

Page 12: ...e en place dans le corps centrez le ressort sur le si ge et ins rez le couvercle et le module de soupape de d charge ensemble dans l al sage Appuyer sur le couvercle pour assurer un alignement correct...

Page 13: ...avec de la graisse au silicone approuv e par la FDA 5 Remonter les modules de clapet antiretour Les modules de clapet sont install s dans le corps de vanne le si ge faisant face l entr e de la vanne...

Page 14: ...de d charge lors d une nouvelle installation avec un r gulateur BMS non inclus 88003057 FP RFK BF BMS CFS Trousse de connexion de mise niveau de capteur BMS S ries 009 LF009 LFU009 SS009 U009 Tailles...

Page 15: ...e installation existante fonctionnant avec la communication cellulaire pour envoi d alertes par courriel message texte ou appel vocal 88003062 FP RFK BF CFS Trousse de connexion de mise niveau de capt...

Page 16: ...ctionne pas correctement les autres co ts r sultant des frais de main d uvre des retards du vandalisme de la n gligence de l encrassement caus par des mat riaux trangers des dommages caus s par des co...

Page 17: ...ida til y el correcto funcionamiento del producto AVISO Para Australia y Nueva Zelanda se deben instalar coladores de l nea entre la v lvula de cierre de aguas arriba y la entrada del dispositivo de p...

Page 18: ...producir condiciones de congelaci n el conjunto debe instalarse sobre el piso en un gabinete aislado como se muestra en la figura 2 Para obtener m s informaci n descargue la especificaci n ES WB en wa...

Page 19: ...de la v lvula de alivio puede ocurrir en aplicaciones de servicio sin salida como l neas de alimentaci n de calderas o l neas de composici n de torres de enfriamiento debido a la fluctuaci n de la pr...

Page 20: ...e en su lugar en el cuerpo centre el resorte en el asiento e inserte la cubierta y el m dulo de la v lvula de alivio como una unidad recta en el orificio Presione la cubierta hacia abajo para asegurar...

Page 21: ...la FDA 5 Vuelva a montar los m dulos de la v lvula de retenci n Compruebe que los m dulos est n instalados en el cuerpo de la v lvula con el asiento orientado hacia la entrada de la v lvula Los m dul...

Page 22: ...rolador BMS no incluido 88003057 FP RFK BF BMS CFS Kit de conexi n de retroadaptaci n del sensor del BMS sistema de gesti n del edificio Serie 009 LF009 LFU009 SS009 U009 Tama os de a 1 27 cm a 1 90 c...

Page 23: ...alaci n existente vinculada a una comunicaci n celular para enviar alertas por correo electr nico mensaje de texto SMS o llamada de voz 88003062 FP RFK BF CFS Kit de conexi n de retroadaptaci n del se...

Page 24: ...tamente otros costos resultantes de cargos laborales demoras vandalismo negligencia contaminaci n causada por materiales extra os da os por condiciones adversas del agua productos qu micos o cualquier...

Reviews: