Servicing the Relief Valve 

NOTICE

 

No special tools are required to service assembly sizes 

2½" to 3". 

1.  Detach the activation module, if installed, from the flood sensor 

then remove the sensor from the relief valve. 

2.  Remove the four or six relief valve cover bolts while holding the 

cover down. 

3.  Lift the cover straight off. The stem and diaphragm assembly 

normally remain with the cover as it is removed. The relief valve 

spring is free inside the body at this point. 

4.  The relief valve seat is located at the bottom of the body bore, 

and can be removed, if necessary, for cleaning. The disc can be 

cleaned without disassembly of the relief valve module. If it is 

determined that the relief valve diaphragm and/or disc should be 

replaced, the relief valve module can be readily disassembled 

without the use of special tools. 

NOTICE

 

The disc rubber is molded into the disc holder and is supplied as 

a disc holder assembly. 

5.  To reassemble the relief valve, press the seat firmly into place in 

the body, center the spring on the seat, and insert the cover and 

relief valve module as a unit straight into the bore. Press down 

on the cover to assure proper alignment. Insert and tighten bolts. 

6.  Reattach the flood sensor to the relief valve and mount the 

activation module to the sensor. 

NOTICE

 

If the cover does not press flat against the body, the stem 

assembly is crooked and damage can result. Realign the stem 

and cover before bolts are inserted. 

Test Cock No. 3 

Test Cock No. 2 

Test Cock No. 4 

First Check 

Module 

Assembly 

Second 

Check Module 

Assembly 

Relief Valve 

Assembly 

Water Outlet 

1" - 2" 

Cover 

Cover O-ring 

Diaphragm 

Stem & Diaphragm 

Assembly 

Retainer 

Seat 

Seat O-ring 

Body 

Relief Valve

Service Parts Kit 

Test Cock No. 2 

Test Cock No. 3 

Test Cock No. 4 

Ball Type 

Test Cocks 

Second Check 

Module Assembly 

Reduced Pressure Zone 

Water Outlet

Relief Valve 

Assembly 

First Check 

Module Assembly 

2½" – 3" 

Cover O-ring 

Diaphragm 

Stem Assembly 

Retainer 

Seat 

Seat O-ring 

Relief Valve Service 

Parts Kit 

Spring 

Flow Tube O-ring 

Summary of Contents for 009 Series

Page 1: ...f the product s internal components helps assure maximum life and proper product function NOTICE For Australia and New Zealand line strainers should be installed between the upstream shutoff valve and...

Page 2: ...he assembly should be installed above ground in an insulated enclosure as shown in Figure 2 For more information download the ES WB specification at watts com The assembly must be installed in an acce...

Page 3: ...lear remove the first check valve and clean thoroughly NOTICE Periodic relief valve discharge may occur on dead end service applications such as boiler feed lines or cooling tower makeup lines due to...

Page 4: ...lder assembly 5 To reassemble the relief valve press the seat firmly into place in the body center the spring on the seat and insert the cover and relief valve module as a unit straight into the bore...

Page 5: ...ew assembly from the repair kit O rings should be cleaned or replaced as necessary and lightly greased with the FDA approved silicon grease 5 Reassemble the check valve modules Check modules are insta...

Page 6: ...n the relief valve of a new installation working with a BMS controller not included 88003057 FP RFK BF BMS CFS BMS Sensor Retrofit Connection Kit Series 009 LF009 LFU009 SS009 U009 Sizes to Includes f...

Page 7: ...of an existing installation working with cellular communication to send alerts by email message SMS text message or voice call 88003062 FP RFK BF CFS Cellular Sensor Retrofit Connection Kit Series 009...

Page 8: ...hich is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chem...

Page 9: ...e du produit et son bon fonctionnement AVIS En Australie et en Nouvelle Z lande les cr pines de conduite doivent tre install es entre le robinet d arr t en amont et l entr e du dispositif de pr ventio...

Page 10: ...nditions de gel peuvent se produire l ensemble doit tre install au dessus du sol dans une enceinte isol e conform ment la figure 2 Pour plus d informations t l chargez la sp cification ES WB l adresse...

Page 11: ...iodique de la soupape de d charge peut se produire dans les applications de service aux extr mit s telles que les conduites d alimentation des chaudi res ou les conduites d appoint des tours de refroi...

Page 12: ...e en place dans le corps centrez le ressort sur le si ge et ins rez le couvercle et le module de soupape de d charge ensemble dans l al sage Appuyer sur le couvercle pour assurer un alignement correct...

Page 13: ...avec de la graisse au silicone approuv e par la FDA 5 Remonter les modules de clapet antiretour Les modules de clapet sont install s dans le corps de vanne le si ge faisant face l entr e de la vanne...

Page 14: ...de d charge lors d une nouvelle installation avec un r gulateur BMS non inclus 88003057 FP RFK BF BMS CFS Trousse de connexion de mise niveau de capteur BMS S ries 009 LF009 LFU009 SS009 U009 Tailles...

Page 15: ...e installation existante fonctionnant avec la communication cellulaire pour envoi d alertes par courriel message texte ou appel vocal 88003062 FP RFK BF CFS Trousse de connexion de mise niveau de capt...

Page 16: ...ctionne pas correctement les autres co ts r sultant des frais de main d uvre des retards du vandalisme de la n gligence de l encrassement caus par des mat riaux trangers des dommages caus s par des co...

Page 17: ...ida til y el correcto funcionamiento del producto AVISO Para Australia y Nueva Zelanda se deben instalar coladores de l nea entre la v lvula de cierre de aguas arriba y la entrada del dispositivo de p...

Page 18: ...producir condiciones de congelaci n el conjunto debe instalarse sobre el piso en un gabinete aislado como se muestra en la figura 2 Para obtener m s informaci n descargue la especificaci n ES WB en wa...

Page 19: ...de la v lvula de alivio puede ocurrir en aplicaciones de servicio sin salida como l neas de alimentaci n de calderas o l neas de composici n de torres de enfriamiento debido a la fluctuaci n de la pr...

Page 20: ...e en su lugar en el cuerpo centre el resorte en el asiento e inserte la cubierta y el m dulo de la v lvula de alivio como una unidad recta en el orificio Presione la cubierta hacia abajo para asegurar...

Page 21: ...la FDA 5 Vuelva a montar los m dulos de la v lvula de retenci n Compruebe que los m dulos est n instalados en el cuerpo de la v lvula con el asiento orientado hacia la entrada de la v lvula Los m dul...

Page 22: ...rolador BMS no incluido 88003057 FP RFK BF BMS CFS Kit de conexi n de retroadaptaci n del sensor del BMS sistema de gesti n del edificio Serie 009 LF009 LFU009 SS009 U009 Tama os de a 1 27 cm a 1 90 c...

Page 23: ...alaci n existente vinculada a una comunicaci n celular para enviar alertas por correo electr nico mensaje de texto SMS o llamada de voz 88003062 FP RFK BF CFS Kit de conexi n de retroadaptaci n del se...

Page 24: ...tamente otros costos resultantes de cargos laborales demoras vandalismo negligencia contaminaci n causada por materiales extra os da os por condiciones adversas del agua productos qu micos o cualquier...

Reviews: