CHAPTER 8:
PARAMETER SUMMARY
8-4
Para-
meters
Explanation Settings
Factory
Setting
Actual
Setting
00: Digital keypad
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
02-10 Source of the Master
Frequency
Command (FCHA)
!
04: RS-485 communication interface
01
00: Digital keypad or Inc./Dec. Frequ.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
02-11
Source of the Auxiliary
Frequency Command (FCHB)
!
04: RS-485 communication interface
02
00: Master fre auxiliary
frequency
02-12
Combination of the Master and
Auxiliary Frequency Command
!
01: Master frequency - auxiliary
frequency
00
00: Digital keypad or Inc./Dec. Frequ.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 communication interface
05: RS-485 communication interface. It
won’t memorize the frequency.
02-13 Source of Second Frequency
Command
!
06: Combined usage of the master and
auxiliary frequency command
02-10, 02-11,02-12
02
00: Determined by digital keypad
01: Master frequency determined by
external terminal, keypad STOP
enabled.
02: Master Frequency determined by
external terminal, keypad STOP
disabled.
03: Master Frequency determined by
RS-485 communication interface,
keypad STOP enabled.
02-14 Source of Second Operation
Command
!
04: Master Frequency determined by
RS-485 communication interface,
keypad STOP disabled.
01
02-15 Keyboard Frequency
Command
!
0.00 ~ 400.00Hz
50.00