![Watt Drive V2500 Series Manual Download Page 43](http://html1.mh-extra.com/html/watt-drive/v2500-series/v2500-series_manual_3740110043.webp)
8
8-3
Group 2: Operation Method Parameters
Para-
meters
Explanation Settings
Factory
Setting
Actual
Setting
00: Digital keypad or Inc./Dec. Frequ.
01: 0 to +10Vdc from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 communication interface
05: RS-485 communication interface. It
won’t memorize the frequency.
02-00 Source of First Frequency
Command
06: Combined usage of the master and
auxiliary frequency command
02-10, 02-11,02-12
01
00: Determined by digital keypad
01: Master frequency determined by
external terminal, keypad STOP
enabled.
02: Master Frequency determined by
external terminal, keypad STOP
disabled.
03: Master Frequency determined by
RS-485 communication interface,
keypad STOP enabled.
02-01 Source of First Operation
Command
04: Master Frequency determined by
RS-485 communication interface,
keypad STOP disabled.
01
00: Ramp Stop; E.F. coast stop
01: Coast Stop; E.F. coast stop
02: Ramp Stop; E.F. ramp stop
02-02 Stop
Method
03: Coast Stop; E.F. ramp stop
00
1 – 5 HP: 01-15kHz
05
7.5 – 22 HP: 01-15kHz
05
30 – 60 HP: 01-09kHz
04
02-03 PWM Carrier Frequency
75 – 100 HP: 01-09kHz
04
00: Enable REV operation
01: Disable REV operation
02-04 Motor Direction Control
02: Disabled FWD operation
00
00: FWD/STOP, REV/STOP
01: FWD/REV, RUN/STOP
02-05 2-wire/3-wire Operation
Control Modes
02: 3-wire Operation
00
00: Disable
02-06 Line Start Lockout
01: Enable
01
00: Decelerate to 0 Hz
01: Stop immediately and display “EF”
02-07 Loss
of
ACI
Signal
02: Continue operation by last
frequency command
01
00: Based on accel/decel time
02-08 Up/Down Key Mode /
Jog mode
01: Constant speed/msec (02-09)
00
02-09
The Accel/Decel Speed of the
UP/DOWN Key with Constant
Speed
0.01~1.00 Hz/msec
0.01