8
8-5
Group 3: Output Function Parameters
Para-
meters
Explanation Settings
Factory
Setting
Actual
Setting
01: AC Drive Operational
02: Master Freq. Attained
03-00 Multi-Function Output (Relay
Output)
03: Zero Speed
04: Over Torque Detection
05: Base-Block (B.B.) Indication
06: Low-Voltage Indication
03-01 Multi-Function Output DO1
07: AC Drive Operation Mode (1 = drive
operation by terminals)
08: Fault Indication
09: Desired Freq. Attained 1
10: PLC Program Running
03-02 Multi-Function Output DO2
11: PLC Program Step Completed
12: PLC Program Completed
13: PLC Program Operation Paused
14: Terminal Count Value Attained
15: Preliminary Count Value Attained
16: Auxiliary Motor No.1
17: Auxiliary Motor No.2
18: Auxiliary Motor No.3
19: Heat Sink Overheat Warning
20: AC Drive Ready
21: Emergency Stop
Indication
22: Desired Frequency Attained 2
23: Software Braking Chopper Signal
24: Zero Speed Output Signal
25: Low-current Detection
26: Operation indication (H>=Fmin)
27: Feedback signal error
28: User-defined low-voltage Detection
03-03
Multi-Function Output DO3
00: No functions
08
01
02
20
03-04 Desired Freq. Attained 1
0.00 to 400.00 Hz
0.00
00: Output frequency (0 – Fmax)
01: Output current (0 – 250%)
02: Output voltage (0 – Vmax)
03: Output frequency command (0–Fmax)
04: Output motor speed (0 – Fmax)
03-05 Analog Output Signal
05: Load power factor
00
03-06 Analog Output Gain
!
01 to 200%
100
03-07 Digital Frequency Output
Multiplying Factor
!
01 to 20
01
03-08 Terminal Count Value
00 to 65500
00
03-09 Preliminary Count Value
00 to 65500
00
03-10 Desired Freq. attained 2
0.00 to 400.00 Hz
0.00
00: Preliminary count value attained, no
EF display.
03-11 EF Display (when Preliminary
Count Value Attained)
01: Preliminary count value attained, EF
display.
00
00: Always fan on
01: Power off 1 minute later, fan off
02: Run and fan on, stop and fan off
03-12 Fan Control
03: Preliminary temperature attained, Fan
start to run
01