Group 9: Communication Parameters
Para-
meters
Explanation Settings
Factory
Setting
Actual
Setting
09-00 Communication
Address
!
1 to 254
1
00: Baud Rate 4800bps
01: Baud Rate 9600bps
02: Baud Rate 19200bps
09-01 Transmission
Speed
!
03: Baud Rate 38400bps
01
09-02 Transmission Fault
Treatment
!
00: Warn and keep Operating
01: Warn and Ramp to Stop
02: Warn and Coast to Stop
03: No warning and keep Operating
03
0.0 ~ 60.0 second
09-03 Timeout
Detection
!
0.0: Disable
0.0
00: 7,N,2 (Modbus, ASCII)
01: 7,E,1 (Modbus, ASCII)
02: 7,O,1 (Modbus, ASCII)
03: 8,N,2 (Modbus, RTU)
04: 8,E,1 (Modbus, RTU)
09-04 Communication Protocol
!
05: 8,O,1 (Modbus, RTU)
00
09-05 HMI Register 1
!
00 to 65535
00
09-06 HMI Register 2
!
00 to 65535
00
09-07
Response Delay Time after
AC-drives receives
communication command
00 ~ 200ms
00