5
5-3
Para-
meter
Explanation Settings
Factory
Setting
Actual
Setting
4-03 Potentiometer Reverse
Motion Enable
d0: Forward Motion Only
d1: Reverse Motion enabled
d0
4-04 Multi-Function Digital Input
Terminal 1 (DI1, DI2)
d0: Parameter Disable
d1: DI1=FWD/STOP, DI2=REV/STOP
d2: DI1=FWD/REV, DI2=RUN/STOP
d3: 3-wire Operation Control Mode
d1
4-05 Multi-Function Digital Input
Terminal 2 (DI3)
d4: E.F. External Fault Input (N.O.)
d5: E.F. External Fault Input (N.C.)
d6: Reset
d7: Multi-Step Speed Command 1
d8: Multi-Step Speed Command 2
d6
4-06 Multi-Function Digital Input
Terminal 3 (DI4)
d9: Multi-Step Speed Command 3
d10: Jog Operation
d11: Acceleration/deceleration Speed
Inhibit (Suspend Acc./Dec.)
d12: First or Second Acceleration/
deceleration Time Selection
d7
4-07 Multi-Function Digital Input
Terminal 4 (DI5)
d13: Base-Block (B.B.) (N.O.)
d14: Base-Block (B.B.) (N.C.)
d15: Increase Master Frequency
d16: Decrease Master Frequency
d17: Run PLC Program
d8
4-08 Multi-Function Digital Input
Terminal 5(DI6)
d18: Pause PLC Program
d19: Counter Trigger Signal
d20: Counter Reset
d21: Select ACI / Deselect AVI
d22: Disable PID function
d23: JOG FWD
d24: JOG REV
d25: The source of master frequency is
AVI.
d26: The source of master frequency is
ACI.
d12
Groupe 5: Multi-Step Speed and PLC Parameters
Groupe 6: Protection Parameters
Groupe 7: Motor Parameters
7-00 Motor Rated Current
!
d30 to d120% (% of Drive
’
s Rated
Current)
d85
7-01
Motor No-Load Current
d0 to d90% (% of Drive
’
s Rated Current)
d50
Groupe 8: Special Parameters
Groupe 9: Communication Parameters
Groupe A: PID Control Parameters