CHAPTER 5’:
QUICK START GUIDE
5-2
Groupe 2: Operation Method Parameters
Para-
meter
Explanation Settings
Factory
Setting
Actual
Setting
2-00 Source of Frequency
Command
d0: Master Frequency input determined
by digital keypad. (record the
frequency of power loss and it can do
analog overlap plus)
d1: Master Frequency determined by
analog signal DC 0V-10V (external
terminal AVI). (won’t record the
frequency of power loss and it can’t
do analog overlap plus)
d2: Master Frequency determined by
analog signal DC 4mA - 20mA
(external terminal AVI). (won’t record
the frequency of power loss and it
can’t do analog overlap plus)
d3: Master Frequency determined by
Potentiometer on the digital keypad.
(won’t record the frequency of power
loss and it can do analog overlap
plus)
d4: Master Frequency operated by RS-
485 serial communication interface.
(record the frequency of power loss
and it can do analog overlap plus)
d5: Master Frequency operated by RS-
485 serial communication interface.
(won’t record the frequency of power
loss and it can do analog overlap
plus)
d1
2-01 Source of Operation
Command
d0: by Digital Keypad
d1: by external terminals, keypad STOP
enabled
d2: by external terminals, keypad STOP
disabled
d3: by RS-485 communication interface,
keypad STOP enabled
d4: by RS-485 communication interface,
keypad STOP disabled
d1
Groupe 3: Output Function Parameters
Groupe 4: Input Function Parameters
Para-
meter
Explanation Settings
Factory
Setting
Actual
Setting
4-00 Potentiometer Bias Frequ.
!
d 0.0 to d 100.0%
d0.0
4-01 Potentiometer Bias Polarity
!
d0: Positive Bias
d1: Negative Bias
d0
4-02 Potentiometer Frequency
Gain
!
d1 to d200 %
d100