Speed: analogue output (J1) (Un only)
A current analogue signal within the range 4-20mA is
available between the O/P (output) terminal and the
GND terminal. The current is fixed and directly
proportional to the pump speed. 20mA = maximum
speed, 4mA = zero speed.
There is also an option to match the scale of the 4-
20mA input if this has been reconfigured by the user.
This option is available in the Control settings menu.
Note:
If the mA output is to be used for reading from a
multimeter (set on mA), a 250Ω resistor is required in
series.
4-20mA
GND
2
J1
O/P
1
Earth shielding terminals
4.8mm spade terminals are supplied for earth shielding of
cables. The input cable and output cable earths can be
connected to either terminal.
Keep 4-20mA and low voltage signals separate from mains power. Use
separate glanded input cables.