8 bit
Byte 3
Min speed (high byte of 16-bit unsigned)
8 bit
Byte 4
Min speed (low byte of 16-bit unsigned)
8 bit
Byte 5
Max speed (high byte of 16-bit unsigned)
8 bit
Byte 6
Max speed (low byte of 16-bit unsigned)
8 bit
Byte 7
Fail safe mode configuration
8 bit
Byte 8
Fail safe speed (high byte of 16-bit unsigned)
8 bit
Byte 9
Fail safe speed (low byte of 16-bit unsigned)
Examples: Ext_User_Prm_Data_Const(0) =
Pump
type
Pump
head
Fieldbus
min speed
set seed
(high byte)
Fieldbus
min speed
set seed
(Low byte)
Fieldbus
Max
speed
(high
byte)
Fieldbus
Max
speed
(low
byte)
Fail
safe
Fail
safe
speed
(high
byte)
Fail
safe
speed
(low
byte)
0x02
0x40
0x00
0x00
0x00
0x00
0x00 0x00
0x00
= 630 with 620R
head
0x02
0x40
0x01
0xF4
0x00
0x00
0x00 0x00
0x00
= 630 with 620R
head with minimum
speed set and
50RPM min speed
0x02
0x40
0x00
0x00
0x05
0xDC 0x00 0x00
0x00
= 630 with 620R
head with
maximum speed set
at 150RPM
0x02
0x40
0x00
0x00
0x00
0x00
0x01 0x00
0x00
= 630 with 620R
head with failsafe set
at last demanded
speed
0x02
0x40
0x00
0x00
0x00
0x00
0x02 0x02
0xEE
= 630 with 620R
head with failsafe set
at 12.8rpm
Pump type
Value
Pump
0x00
530 (DEFAULT)
0x01—
530
0x02—
630
0x03—
730
42
m-630un-en-08