Setup
MLS User’s Guide 79
Heat/Cool Output Filter
Use this menu to dampen the heat or cool output's response. The output
responds to a step change by going to approximately 2/3 of its final
value within the number of scans you set here.
Selectable range: 0-255. Setting the output filter to 0 turns it off.
Heat/Cool Spread
Use this menu to set the spread between the heat and cool output and the
spread of the On/Off control action.
Selectable range: The spread ranges from 0 to 255, 25.5, 2.55, .255 or
.0255, depending on the way you set up the input menus.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
07 HEAT CONTROL
FILTER ? 2
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
01 HEAT
SPREAD ? 5
º
F