104 MLS User’s Guide
Tuning and Control
Setting Up and Tuning PID Loops
To start your process after installation, tune the control loops and set
them to automatic control. If the loop is already in automatic control
mode and controlling the process, set the loop to manual control. Then
you can tune it without upsetting the process. However, if you don’t
mind minor process fluctuations, you can tune the loop in automatic
control mode.
NOTE
Remember that tuning is a slow process. After you
change a PID parameter, allow time (20 minutes
for most processes) before you make another
change.
Proportional Band (PB) Settings
This table shows PB settings for several setpoints.
Setting the PB: a General Rule
Set the PB to 10% of the setpoint below 1000
º
and 5% of the setpoint
above 1000
º
. This setting is useful as a starting value.
Temperature
Setpoint
PB
Temperature
Setpoint
PB
Temperature
Setpoint
PB
-100 to 99
20
1100 to 1199
75
2200 to 2299
135
100 to 199
20
1200 to 1299
80
2300 to 2399
140
200 to 299
30
1300 to 1399
85
2400 to 2499
145
300 to 399
35
1400 to 1499
90
2500 to 2599
150
400 to 499
40
1500 to 1599
95
2600 to 2699
155
500 to 599
45
1600 to 1699
100
2700 to 2799
160
600 to 699
50
1700 to 1799
105
2800 to 2899
165
700 to 799
55
1800 to 1899
110
2900 to 2999
170
800 to 899
60
1900 to 1999
120
3000 to 3099
175
900 to 999
65
2000 to 2099
125
3100 to 3199
180
1000 to 1099
70
2100 to 2199
130
3200 to 3299
185
Summary of Contents for MLS-PM
Page 13: ...Contents MLS User s Guide vi...
Page 17: ...4 MLS User s Guide Overview...
Page 59: ...46 MLS User s Guide Installation...
Page 120: ...Tuning and Control MLS User s Guide 107...
Page 121: ...108 MLS User s Guide Tuning and Control...
Page 131: ...118 MLS User s Guide Troubleshooting...
Page 143: ...Glossary MLS User s Guide 130...