10 MLS User’s Guide
Introduction
Miscellaneous Specifications
Serial Interface
System Power Requirements
Environmental Specifications
Dimensions and Weight
Type
RS-232 3-wire or RS-485 4-wire.
Isolation
RS-232: None
RS-485: To EIA RS-485 specification.
Baud Rate
2400 or 9600, user selectable.
Error Check
BCC or CRC, user selectable.
Number of Controllers
1 with RS-232 communications, 32 with RS-485 communications,
16 with open frame units.
Protocol
Form of ANSI X3.28-1976, (D1, F1) compatible with Allen-Brad-
ley PLC, full duplex.
MLS-PM supply input
10-28 Vdc at <1 amp
MLS-AIM supply input
4.75 to 5.25 Vdc at <0.5 amp, supplied by
MLS-PM
MLS-PS system power supply
Input: 120 Vac at 0.5 amp
Output: 12 Vdc at 1 amp
Storage Temperature
-20 to 70
º
C
Operating Temperature
0 to 50
º
C
Humidity Conditions
10 to 95% non-condensing
MLS-PM
1.75 lbs., 1.89" x 3.78" x 6.75" (0.8 kg, 4.75 cm x 10 cm x 17
cm.)
MLS-AIM-TB
& AIM cards
1.50 lbs., 5.0" x 6.50" x 5.50" (0.7 kg, 12.5 cm x 16.25 cm x
13.75 cm.)
MLS-PS
1.50 lbs., 1.90" x 8.10" x 4.90" (0.7 kg, 4.75 cm x 20.25 cm x
12.25 cm.)
RTB
.5 lbs, 5.0’’ x 3.0’’ x 2.25’’ (.227 kg, 12.7 cm x 7.6 cm x 5.7 cm.)
Summary of Contents for MLS-PM
Page 13: ...Contents MLS User s Guide vi...
Page 17: ...4 MLS User s Guide Overview...
Page 59: ...46 MLS User s Guide Installation...
Page 120: ...Tuning and Control MLS User s Guide 107...
Page 121: ...108 MLS User s Guide Tuning and Control...
Page 131: ...118 MLS User s Guide Troubleshooting...
Page 143: ...Glossary MLS User s Guide 130...