Watlow DIN-A-MITE C User Manual Download Page 4

DIN-A-MITE C Ordering Information

To order, complete the code number on the right with the information below:

Style C

solid-state power controller

Phase

1

= single-phase, 1 controlled leg

2

= 3-phase, 2 controlled legs

3

= 3-phase, 3 controlled legs (use with four-wire wye)

8

= 2 independent zones (input control C, K)

9

= 3 independent zones (input control C, K)

Cooling and Current Rating Per Leg

0

= Natural convection standard DIN rail or panel heatsink

1

= Fan-cooled 120V

Å

(ac) standard DIN rail or panel heatsink

2

= Fan-cooled 240V

Å

(ac) standard DIN rail or panel heatsink

3

= Fan-cooled 24V

Î

(dc) fan standard DIN rail or panel heatsink

T = Natural convection through-wall or cabinet heatsink (UL 50)

Line and Load Voltage

02 = 24 to 48V

Å

(ac) (Input Control Signal C, F, or K only)

12 = 100 to 120V

Å

(ac) (Input Control Signal L, P or S only)

20 = 200 to 208V

Å

(ac) (Input Control Signal L, P or S only)

24 = 120 to 240V

Å

(ac) (Input Control Signal C, F or K only); 

230 to 240V

Å

(ac) (Input Control Signal L, P or S only)

27 = 277V

Å

(ac) (Input Control Signal L, P or S only)

40 = 400V

Å

(ac) (Input Control Signal L, P or S only)

48 = 480V

Å

(ac) (Input Control Signal L, P or S only)

60 = 277 to 600V

Å

(ac) (Input Control Signal C, F or K only); 

600V

Å

(ac) (Input Control Signal L, P or S only)

Input Control Signal

C0 = 4.5 to 32V

Î

(dc) contactor

K1 = 22 to 26V

Å

contactor

K2 = 100 to 120V

Å

contactor

K3 = 200 to 240V

Å

contactor

F0 = Proportional 4 to 20 mA (loop powered)
L(0 to 5) = Phase angle with current limiting (DC1 only, Alarm 0 only,

includes one current transformer - Single phase only)

P(0 to 5) = Phase angle (DC1 only, Alarm 0 only - Single phase only)
S(0 to 5) = Single-cycle variable time base
(Select one of the following input options for L, P, S, (0 to 5))

0 = 4 to 20mA 
1 = 12 to 20mA (for Input Control Signal option S only)
2 = 0 to 20mA
3 = 0 to 5V

Î

(dc) proportional

4 = 1 to 5V

Î

(dc) proportional

5 = 0 to 10V

Î

(dc) proportional

Alarm

0

= No alarm

S = Shorted-SCR alarm (not available on Phase options 8 & 9 or Control options L & P)
H = Open-heater and shorted-SCR alarm (for Input Control Signal option S only)

User Manual Language

0

= English

1

= German

2

= Spanish

3

= French

Custom Part Numbers

00 = Standard part
1X = 1-second soft start (control option P, L)
XX = Any letter or number, custom options, labeling, etc.

4

WATLOW DIN-A-MITE Style C User's Manual

__ __ __ __ - __ __ __ __ - __ __ __ __

D C

Current Rating Table

Model

Current 

(first 4 digits 

at 50°C

of part number) (122°F)

DC10

55 A

DC1T

62 A

DC11, DC12, DC13

75 A

DC20, DC80

40 A

DC2T, DC8T

46 A

DC21, DC22, DC23

65 A

DC81, DC82, DC83
DC30, DC90

30 A

DC3T, DC9T

35 A

DC31, DC32, DC33

55 A

DC91, DC92, DC93

Note:

• Recommended fusing 

options to meet 200KA
SCCR, type 1 and 2 
approved.  All other 
fuse and SCR com-
binations are de-
faulted to 5KA SCCR 
per UL508A and NEC 
guidelines.

Not CE compliant
for conducted or
radiated emissions

Semiconductor Fuses for Applications Through 600V

Å

(ac):

Semiconductor 

Watlow Fuse 

Bussman Fuse 

Watlow Holder

Ferraz Holder

Fuse Rating 

P/N

P/N

P/N

P/N

30A

17-8030

FWP30A14F

17-5114

USM141i

40A

17-8040

FWP40A14F

17-5114

USM141i

50A

17-8050

FWP50A14F

17-5114

USM141i

63A

17-8063

FWP63A22F

17-5122

US221i

80A

17-8080

FWP80A22F

17-5122

US221i

100A

17-8100

FWP100A22F

17-5122

US221i

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for DIN-A-MITE C

Page 1: ...DIN A MITE power controller includes single phase 3 phase 2 leg and 3 phase 3 leg 120 to 600V ac operation Current switching capabilities range from 30 to 80A depending on the model ordered See the o...

Page 2: ...gle with current limit Input Control Signal Types P and L are not CE approved UL 50 Type 4X Enclosure and UL ANSI ISA 12 12 01 Temperature Code T4A The through wall heatsink package is suitable for us...

Page 3: ...ed 0 to 100 08 5362 Alarm option is not available on phase angle type P or type L Resolution Better than 0 1 of input span with respect to output change Control Mode Zero Cross Input Control Signal Ty...

Page 4: ...se only P 0 to 5 Phase angle DC1 only Alarm 0 only Single phase only S 0 to 5 Single cycle variable time base Select one of the following input options for L P S 0 to 5 0 4 to 20mA 1 12 to 20mA for In...

Page 5: ...soft start and line voltage compensation This model will work with a linear voltage input a linear current source input or a potentiometer input This is single phase only Alarms not available on phase...

Page 6: ...nto place If the DIN A MITE does not snap into place check to see if the rail is bent 4 Mount the cooling fins vertically 3 WARNING Only authorized and qualified personnel should be allowed to install...

Page 7: ...flow and wire bending radius 102 mm 4 0 in clearance for air flow and wire bending radius 150 mm 5 89 in Rail Release Tab pull down 44 mm 1 73 in 57 mm 2 26 in 127 mm 5 00 in 79 mm 3 10 in 102 mm 4 0...

Page 8: ...atsink 4 Mount the heatsink vertically Torque to 2 26 to 2 82 Nm 20 to 25 in lb Ground lug 2 8 GA M5 0 8 by 10 mm 8 M5 Internal Tooth Lock Washer 8 included 178 mm 7 00 in 122 mm 4 81 in Panel Opening...

Page 9: ...5 16 17 18 19 20 1 2 3 4 5 6 Signal Alarm Gain Bias Open Heater Limit Adjustment Potentiometers 4 to 20mA dc Input 7 8 9 4 5 to 32V dc Input 7 8 9 Zone 1 Zone 2 Zone 3 Note Use tool Bourns H91 to adju...

Page 10: ...Zone 2 Zone 3 1k Potentiometer Input Use with 0 to 5V dc Input 4 to 20mA and Linear Voltage Input 1 3 For models DC 1 2 3 _ _ _ L P S _ _ _ _ _ Auto and Manual Input Application 4 to 20mA dc signal fr...

Page 11: ...power 4 Turn on the power to the DIN A MITE 5 Gradually increase the input signal 6 Adjust the current limit potentiometer clockwise until the current to the load is measurable The current limit indic...

Page 12: ...o 20mA output or 5V for 0 to 5V output 2 Adjust the open heater alarm adjustment potentiometer until the alarm indicator light on the front panel is full on with no intermittent cycling 3 Slowly adjus...

Page 13: ...ge to equipment and personal injury or death NOTE The shorted SCR alarm option is not available with phase angle units Torque Guidelines Properly torque line and load terminals to 2 7 Nm 24 in lb Reto...

Page 14: ...jury or death Torque Guidelines Properly torque line and load terminals to 2 7 Nm 24 in lb Retorque after 48 hours to minimize wire cold flow Retorque line and load terminals every 3 to 6 months L1 L2...

Page 15: ...15 16 17 18 19 20 Gain Bias Open Heater Limit ALM ALM CT1 CT1 CT2 CT2 CT3 CT3 4 5 6 1 2 3 Signal Alarm Zone 1 Zone 2 Zone 3 Heater 2 Heater 3 Heater 1 L2 L2 L2 Limit Control Contacts if required Semic...

Page 16: ...f you plan to wire multiple DIN A MITE alarm outputs you need to include an intermediate relay for each DIN A MITE used System Wiring Example Alternative Latching Alarm Circuit If there is a need for...

Page 17: ...SCR alarm will energize a triac on board the DIN A MITE output An open heater or partial open heater state is detected when a command signal is present and a reduced or no output current is detected T...

Page 18: ...oltage Variations EN 61000 3 2 2009 Harmonic Current Emissions Reviewed to IEC 61000 3 2 2014 EN 61000 3 3 2013 Voltage Fluctuations and Flicker3 16A EN 61000 3 11 2000 Voltage Fluctuations and Flicke...

Page 19: ...to death for personnel WARNING All filter installation and wiring must be performed by qualified personnel and conform to local and national electrical codes In line power filters have been shown to p...

Page 20: ...number Detailed description of the problem Any special instructions Name and phone number of the person returning the product 2 Prior approval and an RMA number from the Customer Service Department is...

Reviews: