Watlow DIN-A-MITE C User Manual Download Page 12

12

WATLOW DIN-A-MITE Style C User's Manual

 

Alarm Relay 

or Indicator

V~

120 or 240V~

@ 300mA maximum 

energizes on alarm

1A

7
8
9

10
11
12
13
14
15
16
17
18
19
20

1           2          3

4

Signal

Alarm

Gain

Bias

Open

Heater

Limit

+

-

+

-

+

-

ALM

ALM

CT1

CT1

CT2

CT2

CT3

CT3

Adjustment

Potentiometers

Triac

Zone

1

Zone 

2

Zone

3

ALM = Alarm
CT = Current Transformer

Current

Transformer 

(CT)

Heater

Load Wire

5

6

Single-phase Alarm

Non-latching Alarm Option
DC _ _ - _ _ _ _ - [H, S] _ _ _ 

NOTE:If you plan to wire
 multiple  DIN-A-MITE
alarm outputs, you need
to include an
intermediate relay for
each DIN-A-MITE used.

The Watlow DIN-A-MITE alarm option provides
a common alarm output for open-heater  or
shorted SCR conditions. 

This is a non-latching

alarm.

• A shorted SCR alarm is detected when there is
no command signal and a load current is
detected. The alarm output is then energized.

• An open-heater or partial open-heater state is
detected when a command signal is present and
a reduced or no output current is detected. The
alarm output is then energized.

Setup Procedure for Open-Heater Alarm

(For Input Control Signal type S option only)

1. With the temperature control wired to the
DIN-A-MITE SCR power control, set the
temperature control output to “full on” (20mA
for 4 to 20mA output, or 5V for 0 to 5V output).

2. Adjust the open heater alarm adjustment
potentiometer until the alarm indicator light on
the front panel is full on, with no intermittent
cycling.

3. Slowly adjust the potentiometer until the
open heater indicator light just turns full off,
with no intermittent cycling.

If you are getting false alarms, the adjustment is
probably set too sensitive and should be re-
adjusted towards the off condition of the open-
heater indicator light. The open heater pot is
adjusted counter clockwise to increase
sensitivity to open heater detect (red light on
sooner) or clockwise to desensitize to open
heater detect (red light on later).

No setup procedure required for shorted SCR alarm.

Load Current -

Single phase load
wire passes through
one CT. Number of
passes through CT:

5 to 9A

2

10 to 65A

1

T1

T2

T3

7
8
9

10
11
12
13
14
15
16
17
18
19
20

Gain

Bias

Open

Heater

Limit

+

-

+

-

+

-

ALM

ALM

CT1

CT1

CT2

CT2

CT3

CT3

Adjustment

Potentiometers

Signal

Alarm

4           5           6

1           2           3

Zone

1

Zone 

2

Zone

3

ALM = Alarm
CT = Current Transformer

Heater

Current Transformers

white

black

3-phase, 2-leg Open Heater Alarm

NOTE:

Load wires must pass
through each current
transformer in the same
direction.

(Model DC2 _ - _ _ S _ - H _ _ _ )

ç  

Ó

1

Ó

3

ç  

Ó

1

Ó

3

Load Current -

3-phase 2-leg load wire
passes through 2 CTs.
Number of passes
through each:

5 to 6A

7

7 to 9A

6

10 to 14A

4

15 to 19A

3

20 to 33A

2

34A and up

1

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for DIN-A-MITE C

Page 1: ...DIN A MITE power controller includes single phase 3 phase 2 leg and 3 phase 3 leg 120 to 600V ac operation Current switching capabilities range from 30 to 80A depending on the model ordered See the o...

Page 2: ...gle with current limit Input Control Signal Types P and L are not CE approved UL 50 Type 4X Enclosure and UL ANSI ISA 12 12 01 Temperature Code T4A The through wall heatsink package is suitable for us...

Page 3: ...ed 0 to 100 08 5362 Alarm option is not available on phase angle type P or type L Resolution Better than 0 1 of input span with respect to output change Control Mode Zero Cross Input Control Signal Ty...

Page 4: ...se only P 0 to 5 Phase angle DC1 only Alarm 0 only Single phase only S 0 to 5 Single cycle variable time base Select one of the following input options for L P S 0 to 5 0 4 to 20mA 1 12 to 20mA for In...

Page 5: ...soft start and line voltage compensation This model will work with a linear voltage input a linear current source input or a potentiometer input This is single phase only Alarms not available on phase...

Page 6: ...nto place If the DIN A MITE does not snap into place check to see if the rail is bent 4 Mount the cooling fins vertically 3 WARNING Only authorized and qualified personnel should be allowed to install...

Page 7: ...flow and wire bending radius 102 mm 4 0 in clearance for air flow and wire bending radius 150 mm 5 89 in Rail Release Tab pull down 44 mm 1 73 in 57 mm 2 26 in 127 mm 5 00 in 79 mm 3 10 in 102 mm 4 0...

Page 8: ...atsink 4 Mount the heatsink vertically Torque to 2 26 to 2 82 Nm 20 to 25 in lb Ground lug 2 8 GA M5 0 8 by 10 mm 8 M5 Internal Tooth Lock Washer 8 included 178 mm 7 00 in 122 mm 4 81 in Panel Opening...

Page 9: ...5 16 17 18 19 20 1 2 3 4 5 6 Signal Alarm Gain Bias Open Heater Limit Adjustment Potentiometers 4 to 20mA dc Input 7 8 9 4 5 to 32V dc Input 7 8 9 Zone 1 Zone 2 Zone 3 Note Use tool Bourns H91 to adju...

Page 10: ...Zone 2 Zone 3 1k Potentiometer Input Use with 0 to 5V dc Input 4 to 20mA and Linear Voltage Input 1 3 For models DC 1 2 3 _ _ _ L P S _ _ _ _ _ Auto and Manual Input Application 4 to 20mA dc signal fr...

Page 11: ...power 4 Turn on the power to the DIN A MITE 5 Gradually increase the input signal 6 Adjust the current limit potentiometer clockwise until the current to the load is measurable The current limit indic...

Page 12: ...o 20mA output or 5V for 0 to 5V output 2 Adjust the open heater alarm adjustment potentiometer until the alarm indicator light on the front panel is full on with no intermittent cycling 3 Slowly adjus...

Page 13: ...ge to equipment and personal injury or death NOTE The shorted SCR alarm option is not available with phase angle units Torque Guidelines Properly torque line and load terminals to 2 7 Nm 24 in lb Reto...

Page 14: ...jury or death Torque Guidelines Properly torque line and load terminals to 2 7 Nm 24 in lb Retorque after 48 hours to minimize wire cold flow Retorque line and load terminals every 3 to 6 months L1 L2...

Page 15: ...15 16 17 18 19 20 Gain Bias Open Heater Limit ALM ALM CT1 CT1 CT2 CT2 CT3 CT3 4 5 6 1 2 3 Signal Alarm Zone 1 Zone 2 Zone 3 Heater 2 Heater 3 Heater 1 L2 L2 L2 Limit Control Contacts if required Semic...

Page 16: ...f you plan to wire multiple DIN A MITE alarm outputs you need to include an intermediate relay for each DIN A MITE used System Wiring Example Alternative Latching Alarm Circuit If there is a need for...

Page 17: ...SCR alarm will energize a triac on board the DIN A MITE output An open heater or partial open heater state is detected when a command signal is present and a reduced or no output current is detected T...

Page 18: ...oltage Variations EN 61000 3 2 2009 Harmonic Current Emissions Reviewed to IEC 61000 3 2 2014 EN 61000 3 3 2013 Voltage Fluctuations and Flicker3 16A EN 61000 3 11 2000 Voltage Fluctuations and Flicke...

Page 19: ...to death for personnel WARNING All filter installation and wiring must be performed by qualified personnel and conform to local and national electrical codes In line power filters have been shown to p...

Page 20: ...number Detailed description of the problem Any special instructions Name and phone number of the person returning the product 2 Prior approval and an RMA number from the Customer Service Department is...

Reviews: