WATLOW DIN-A-MITE Style C User's Manual

3

Additional Specifications: Phase Angle; Phase Angle Current Limit; & Single Cycle VTB

Operation

• Burst firing (zero-cross) control, single-cycle variable

time base, Type S single-phase and 3-phase. Unit is
not on for more than one full cycle under 50% power
and not off for more than one full cycle above 50%
power.

• Phase angle control, single-phase only

Input Command Signal

• 0 to 20mA, 4 to 20mA, 12 to 20mA, 

Î

(dc), 0 to 5V

Î

, 1

to 5V

Î

, and 0 to 10V

Î

• Input impedance 250

for 4 to 20mA, 5k

for linear

voltage input

Output Voltage

• 100 to 120V

Å

(ac), 200 to 208V

Å

, 230 to 240V

Å

,

277V

Å

, 400V

Å

, 480V

Å

, 600V

Å

, -15%/+10%, 50 or

60 Hz indep/-5% (Input Control Signal Type
L, P and S)

Phase Angle Accuracy

• Output on time is directly proportional to the command

signal.  Output on time is accurate to within 5% of the
command signal input at 25 degrees C ambient.  See
chart below for command signal input to output power
transfer function.  Temperature stability at ambient
temperature is less than 0.25%/degrees C.

Single Cycle VTB Accuracy

• Output power is directly proportional to the command

signal.  Output power is accurate to within 5% of the
command signal input at 25 degrees C ambient.
Temperature stability is less than 0.25%/degrees C
ambient temperature change.

Soft Start 
(Phase Angle Input Control Signal Type P and L)

Typically:
• 5 seconds soft start on power up
• Soft start on thermostat overtemperature
• Soft start on 1/2 cycle drop out detection
• 1 second soft switching on set point change

Options

• Manual Control Kit (1k

Ω, 1 turn

potentiometer with dial

scale labeled 0 to 100%) 08-5362

• Alarm option is 

not

available on phase angle type P or

type L.

Resolution

• Better than 0.1% of input span with respect to output

change.

Control Mode, Zero-Cross

• Input Control Signal Type C: V

Î

(dc) input contactor. 

To increase service life, the cycle time should be less
than 3 seconds.

• Input Control Signal Type K: V

Å

(ac) input contactor.

To increase service life, the cycle time should be less
than 3 seconds.

• Input Control Signal Type F: 4 to 20mA

Î

(dc)

proportional variable time base control.

Input Command Signal

• AC contactor

24V

Å 

±10%, 120V

Å 

+10%/-25%, 240V

Å

(ac)

+10%/-25% @ 25mA maximum per controlled leg

• Do not use the DIN-A-MITE Vac-input models with a

temperature controller that includes an RC snubber
circuit across its output. Remove the RC snubber
circuit before placing the DIN-A-MITE into service.

• DC Contactor

4.5 to 32V

Î

(dc): maximum  current @ 4.5V

Î

(dc) is 6mA per leg. Add 2mA per LED used to the
total current.

• Loop powered linear current

4 to 20mA

Î

(dc): loop-powered. Input Type 

F0 option only. (Requires current source with 8.0V

Î

(dc) available. No more than two inputs connected in
series.)

Linearity (Input Control Signal Type F)

• Full on point 19.5 to 19.9mA

Î

(dc), maximum voltage

of 6.2V peak.

• ±5% input to output power accuracy, 0% to 100% of

span (4.3 to 19.7mA or 12.3 to 19.7mA).

• Temperature stability is less than 0.15%/°C change.

Additional Specifications for Contactors and Proportional Controls

0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

90.0

100.0

0

10

20

30

40

50

60

70

80

90

100

Command Signal Input (%P)

Output (%P)

Phase Angle Command Signal Input to Output Power

Note:

The DIN-A-MITE C was changed in April of

2007 to add the shut down circuitry (fan failure) to
all units shipped. The shut down temperature is
approximately 117C.

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for DIN-A-MITE C

Page 1: ...DIN A MITE power controller includes single phase 3 phase 2 leg and 3 phase 3 leg 120 to 600V ac operation Current switching capabilities range from 30 to 80A depending on the model ordered See the o...

Page 2: ...gle with current limit Input Control Signal Types P and L are not CE approved UL 50 Type 4X Enclosure and UL ANSI ISA 12 12 01 Temperature Code T4A The through wall heatsink package is suitable for us...

Page 3: ...ed 0 to 100 08 5362 Alarm option is not available on phase angle type P or type L Resolution Better than 0 1 of input span with respect to output change Control Mode Zero Cross Input Control Signal Ty...

Page 4: ...se only P 0 to 5 Phase angle DC1 only Alarm 0 only Single phase only S 0 to 5 Single cycle variable time base Select one of the following input options for L P S 0 to 5 0 4 to 20mA 1 12 to 20mA for In...

Page 5: ...soft start and line voltage compensation This model will work with a linear voltage input a linear current source input or a potentiometer input This is single phase only Alarms not available on phase...

Page 6: ...nto place If the DIN A MITE does not snap into place check to see if the rail is bent 4 Mount the cooling fins vertically 3 WARNING Only authorized and qualified personnel should be allowed to install...

Page 7: ...flow and wire bending radius 102 mm 4 0 in clearance for air flow and wire bending radius 150 mm 5 89 in Rail Release Tab pull down 44 mm 1 73 in 57 mm 2 26 in 127 mm 5 00 in 79 mm 3 10 in 102 mm 4 0...

Page 8: ...atsink 4 Mount the heatsink vertically Torque to 2 26 to 2 82 Nm 20 to 25 in lb Ground lug 2 8 GA M5 0 8 by 10 mm 8 M5 Internal Tooth Lock Washer 8 included 178 mm 7 00 in 122 mm 4 81 in Panel Opening...

Page 9: ...5 16 17 18 19 20 1 2 3 4 5 6 Signal Alarm Gain Bias Open Heater Limit Adjustment Potentiometers 4 to 20mA dc Input 7 8 9 4 5 to 32V dc Input 7 8 9 Zone 1 Zone 2 Zone 3 Note Use tool Bourns H91 to adju...

Page 10: ...Zone 2 Zone 3 1k Potentiometer Input Use with 0 to 5V dc Input 4 to 20mA and Linear Voltage Input 1 3 For models DC 1 2 3 _ _ _ L P S _ _ _ _ _ Auto and Manual Input Application 4 to 20mA dc signal fr...

Page 11: ...power 4 Turn on the power to the DIN A MITE 5 Gradually increase the input signal 6 Adjust the current limit potentiometer clockwise until the current to the load is measurable The current limit indic...

Page 12: ...o 20mA output or 5V for 0 to 5V output 2 Adjust the open heater alarm adjustment potentiometer until the alarm indicator light on the front panel is full on with no intermittent cycling 3 Slowly adjus...

Page 13: ...ge to equipment and personal injury or death NOTE The shorted SCR alarm option is not available with phase angle units Torque Guidelines Properly torque line and load terminals to 2 7 Nm 24 in lb Reto...

Page 14: ...jury or death Torque Guidelines Properly torque line and load terminals to 2 7 Nm 24 in lb Retorque after 48 hours to minimize wire cold flow Retorque line and load terminals every 3 to 6 months L1 L2...

Page 15: ...15 16 17 18 19 20 Gain Bias Open Heater Limit ALM ALM CT1 CT1 CT2 CT2 CT3 CT3 4 5 6 1 2 3 Signal Alarm Zone 1 Zone 2 Zone 3 Heater 2 Heater 3 Heater 1 L2 L2 L2 Limit Control Contacts if required Semic...

Page 16: ...f you plan to wire multiple DIN A MITE alarm outputs you need to include an intermediate relay for each DIN A MITE used System Wiring Example Alternative Latching Alarm Circuit If there is a need for...

Page 17: ...SCR alarm will energize a triac on board the DIN A MITE output An open heater or partial open heater state is detected when a command signal is present and a reduced or no output current is detected T...

Page 18: ...oltage Variations EN 61000 3 2 2009 Harmonic Current Emissions Reviewed to IEC 61000 3 2 2014 EN 61000 3 3 2013 Voltage Fluctuations and Flicker3 16A EN 61000 3 11 2000 Voltage Fluctuations and Flicke...

Page 19: ...to death for personnel WARNING All filter installation and wiring must be performed by qualified personnel and conform to local and national electrical codes In line power filters have been shown to p...

Page 20: ...number Detailed description of the problem Any special instructions Name and phone number of the person returning the product 2 Prior approval and an RMA number from the Customer Service Department is...

Reviews: