Technical Data
05.06.2015
75 / 80
Copyright
2013 by: WATERKOTTE GmbH. Subject to changes.
15.2
EcoTouch Ai1 Air (Power Inverter)
EcoTouch Ai1 Air (Power Inverter)
5004.5
5006.5
5008.5
5011.5
5014.5
Outdoor unit
3x 400 V
1x 230 V
PUHZ-SW
40VHA
PUHZ-SW
50VHA
PUHZ-SW
75VHA
PUHZ-SW
100YHA
PUHZ-SW
100VHA
PUHZ-SW
120YHA
Heating capacity (A-15/W35)
kW
3.1
3.5
7.2
7.4
9.6
COP (A-15/W35), EN14511
2.1
2.0
1.9
2.1
2.1
Heating capacity (A-10/W35)
kW
3.8
4.2
8.2
8.8
11.1
COP (A-10/W35), EN14511
2.5
2.4
2.4
2.5
2.4
Heating capacity (A-7/W35)
kW
3.8
4.4
7.0
8.5
11.2
COP (A-7/W35), EN14511
2.8
2.7
2.9
2.9
2.9
Heating capacity (A2/W35)
kW
3.2
4.0
6.0
8.0
9.6
COP (A2/W35), EN14511
3.5
3.2
3.6
3.6
3.6
Heating capacity (A7/W35)
kW
3.3
4.8
6.4
9.0
12.8
COP (A7/W35), EN14511
4.8
4.6
4.7
4.6
4.4
Cooling capacity (cooling) (A35/W18)
kW
3.6
5.0
7.1
10.0
14,0
Power consumption, hot-water heating pump
W
70
70
70
70
70
Heating water flow rate (A2/W35) (∆t=5K )
m³/h
0.7
0.9
1.3
1.8
2.0
Air volume flow
m³/h
2100
2100
3300
6600
6600
Fan motor, max. power consumption
W
40
40
86
2x 60
2x 60
Application limit
A-15/W50 ; A-10/W55 ; A2/W60
Compressor
hermetically sealed, power-controlled
Refrigerant
R410A (pre-charged)
Refrigerant volume
kg
2.1
2.1
3.2
4.6
4.6
Minimum volume of the installation room
(m
3
/ EN 378-1)
m
3
4.8
4.8
7.3
10,5
10.5
Sound power (outdoor module)
2)
dB(A)
62
63
69
70
72
Electrical data
Electrical power supply
(380-415V, 3~, 50Hz)
•
•
Electrical power supply
(220-240V, 1~, 50Hz)
•
•
•
•
Starting current
A
<13
<13
<19
<13
(<27)
1)
<13
Max. operating current
A
<13
<13
<19
<13 (<27)
1)
<13
Max. power consumption
kW
3.14
4.01
4.67
6.13
7.53
Customer-supplied main fuse
A
16
16
25
16 (32)
1)
16
Customer-supplied control fuse
A
10
Electrical resistance heating
kW
6
Domestic hot water tank
Capacity
204 l
Max. operating pressure
10 bar
Tank connections
Cold water / hot water 3/4“ ext.
Interior tank coating
enamelled
Dimensions, weight, connections
Compr. volume Oil filling, Type: ester oil
l
0.5
0.5
0.87
1.4
1.4
Weight of outdoor module
kg
45
45
75
135
135
Weight heat distributor
kg
148
Weight tank, without housing
kg
65
Weight hydraulic module, without housing
kg
48
Heater connections / hot water
1¼”a / ¾“a
Dimensions of indoor unit W x H x D
mm
600 x 1993 x 663
Dimensions of outdoor unit W x H x D
mm
800x600x300
950x943x330
950x1350x330
1)
applies to (V, Phase, Hz) 220-240, 1, 50 ;
2)
the silent mode reduces the noise level -5 dB(A)
For individual technical data and filling capacities of your heat pump
system, please refer to type plate.