Wärtsilä JOVYTEC P 700VA 

– 3kVA 

      BAX 3345 

- 10 -

 

 

 

 

 

JOVYTEC P 1000 

 

Output power 

cos 

 0,7 ind. 

1000VA / 700W 

 

Network supply 

Voltage 

230V  

Input voltage ranges 

168V - 276V (0-100% load) 

140 - 159V (0-70% load) 
120 - 139V (0-40% load) 

Current with standard charger 

4A 

Current with additional charger 

5,2A 

Frequency 

50Hz ±3Hz or 60Hz ±3Hz 

Phase 

Single phase 

Power Factor 

0,98 

External fuse protection 

D01/10A 

 

Battery 
(installed in battery pack inside the 
ups) 

Direct current link voltage 

36V 

Backup time 

10min. at 100% load 

15min. at 80% load 

27min.at 50% load 

Type 

Maintenance free, closed lead acid batteries 

Charging time 

< 8 Stunden for 90% charged battery 

 

Output 

Voltage 

230V Standard (208V / 220V / 240V selectable at the panel) 

Frequency 

Automatic adjustment by ups 

Power factor 

cos 

0,7 ind. 

Phase 

Single phase 

Distorsion  factor 

< 3% at linear load 

Overload behaviour 

100 to 125% for 60 seconds 

125 

– 150% for 10s 

Crest Factor 

3 : 1 

 
Efficiency 

AC to AC 

88 - 98% according to the operation mode 

 

Switch over behaviour 

Power failure 

0ms 

Overload switching 

Automatic overload switching by the ups 

 
Noise level 

At a distance of 1m 

< 45dB(A) 

 

Environment 

Temperature 

0°C to 40°C 

+15 … +25°C (recommended) 

Air humidity 

0% to 95%, non condensing 

Storage at 

… 

20°C (recommended) with Battery 

-20°C to 50°C without Battery 

 

Interfaces 

RS 232-Interface 

 
Optional:  

USB-Interface 
Relay card 
AS/400 - Adapter 
SNMP - Adapter 

Supports power management and diagnosis such as BATTERY 

LOW, UPS ON/OFF 

Software is compatible with operating systems such as: Windows 

95/98/NT/2000/XP, Novell, Unix, etc current operating systems. 

 

Dimensions 
UPS Device

 

Width 

152mm 

Depth 

420mm 

Heights 

238mm 

 
Weight UPS 

 

approx. 9,4 kg 

Weight UPS incl. Battery 

 

approx. 17,4 kg 

Scope of delivery 

Hardware/Software 

UPS unit JOVYTEC P 1000 

Manual BAX 3345E 

Interface cable 

Software UPSMON 

Summary of Contents for JOVYTEC P 1000

Page 1: ...BAX 3345 Operating Manual W rtsil JOVYTEC P 700VA 3kVA...

Page 2: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 2 Index Date Name Revision 0 2014 06 20 Chr Fechteler 14 375 1 2014 10 29 Chr Fechteler 14 600 2 2017 08 14 D Busboom 17 262 3 4 5 6 7 8 9 10...

Page 3: ...part of the contract but simply serve as a source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this ope...

Page 4: ...G AND INDICATING ELEMENTS 21 7 1 LED AND FUNCTION KEYS 21 7 2 PARAMETERS 22 7 3 CONFIGURATION 22 7 4 TABLE OF THE ADJUSTABLE PARAMETERS 23 7 5 AUTOMATIC MANUAL BATTERY TEST 23 7 6 OFFLINE MODE 24 7 7...

Page 5: ...1 TECHNICAL DATA AUTONOMY TIMES 31 13 2 VIEWS 32 13 2 1 BATTERY CABINET B10 B12 32 13 2 2 BATTERY CABINET BM1 33 13 2 3 BATTERY CABINET BM2 33 13 2 4 BATTERY CABINET BM3 33 13 3 CONNECTION 34 13 3 1 B...

Page 6: ...discharging voltage is not reached 1 General notes The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE regulations Provisions of the loca...

Page 7: ...During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating voltag...

Page 8: ...ns that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault in th...

Page 9: ...rsion factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failur...

Page 10: ...factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms...

Page 11: ...factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms...

Page 12: ...factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms...

Page 13: ...rsion factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failur...

Page 14: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 14 238 152 5 Dimensions and views 5 1 JOVYTEC P 700 P 1500...

Page 15: ...5 Relay Card USB Interface option Connector for external Battery Load output socket Cold output socket for consumers 5 2 Rear view JOVYTEC P 700 P 1000 Electronic Stop RS232 Interface TAE Protection C...

Page 16: ...0VA 3kVA BAX 3345 16 USB Interface option 5 3 Rear view JOVYTEC P 1500 Electronic Stop RS 232 Interface TAE Protection Circuit Fan Input Fuse Main Input Plug Relay Card Connector for external Battery...

Page 17: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 17 225 360 5 4 JOVYTEC P 2000 P 3000...

Page 18: ...JOVYTEC P 2000 P 3000 Fan Fan TAE Protection Circuit RS232 Interface Electronic Stop Input Fuse Mains Input Plug Electronic Stop Relay Card USB Interface option Connector for external Battery Output...

Page 19: ...ct socket 3 Connect up the battery cabinet supplied optional for longer autonomy times via the battery connection jack 4 All connecting up work is now complete P L E A S E N O T E Only trained personn...

Page 20: ...pressing the ON OFF button and the message Switching off soon appears in the display and then the message UPS OFF The UPS unit is now shut down Please note The device fans continue to run as long as t...

Page 21: ...s the output voltage etc The formalism is as follows Press the FUNC key on a running UPS unit for 2 seconds to start the menu for the UPS unit parameters Pressing of the ENTER button selects the param...

Page 22: ...lue of the UPS in VA CPU VERSION 3 12 CPU software 7 3 Configuration Use of the function display and the function keys allows diverse settings to be made on the UPS unit The formalism is as follows In...

Page 23: ...uage selection English German French Spanish Italian German Generator mode Generator Generator mode ON OFF OFF Setting RS 232 interface COM control command Setting of RS232 interface ON OFF ON The man...

Page 24: ...1 0 02 51Hz 7 7 1 Free running ON If the input frequency is 49 3Hz this value is within the narrow input frequency range This means that the output frequency is also 49 3Hz synchronised and the UPS u...

Page 25: ...the bypass window has the following values Bypass lower limit 230 V x 1 0 2 230 V x 0 8 184 V bypass upper limit 230 V x 1 0 15 230 V x 1 15 264 5 V A 2 tolerance was selected for the input frequency...

Page 26: ...cessary The UPS switches again to normal operation after a successful battery test Overcharging over charge Continuous tone The batteries are over charged Battery charge voltage too high Contact the s...

Page 27: ...UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of power failure is possible 9 1 Connecting the UPS to the computer Th...

Page 28: ...nic STOP functionality is to be used then the bridge should be removed on the plug and an external switch opener clamped to the rear plug Actuation of the external electronic STOP switch causes the ou...

Page 29: ...mers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be restarted There is still a voltage inside and at the terminals even after the electronic STOP f...

Page 30: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 30...

Page 31: ...000 120 BM3 280 x 680 x 630 80 91 9 JOVYTEC P 1500 0 10 4 JOVYTEC P 1500 6 18 2 JOVYTEC P 1500 30 BM1 152 x 238 x 420 40 58 2 JOVYTEC P 1500 40 BM2 225 x 360 x 425 50 60 4 JOVYTEC P 1500 60 BM3 280 x...

Page 32: ...3 2 Views 13 2 1 Battery Cabinet B10 B12 Battery Cabinet Type Dimensions apporx in mm Weight without Batteries in kg A B C D E B10 470 800 1090 780 470 70 B11 470 800 1340 780 470 80 B12 910 810 1620...

Page 33: ...BM1 BM3 see Table Battery Cabinets Cabinet Socket Cable to UPS System Battery Fuses F1 F2 BATTERIE F1 F2 Air Outlet 240V ZWISCHEN KREISSPANNUNG Plastic Feet Battery Fuses F1 F2 Battery Cable to UPS Sy...

Page 34: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 34 13 3 Connection 13 3 1 Battery Cabinets B10 B11 B12 Battery Fuses Battery terminals F1 F2 X1 X2 PE 1 2 3...

Page 35: ...tery cabinets are fit up with flexible connection wires At the rear of the battery cabinets are two fuses of the battery reachable F1 positive pole F2 negative pole Battery Fuses UPS Device F1 F2 JOVY...

Page 36: ...until the battery is charged up Restoration of mains power after total discharge of the battery At the end of the bridging time the inverter switches off automatically and the consumers are no longer...

Page 37: ...t is located on the left side of the battery rack 4 Unhook the retaining bracket 5 Pull the battery pack out of the UPS unit using the pulling strap Please note that if a power failure occurs now the...

Page 38: ..._________________________________________________________________________________ ______________________________________________________________________________________ _______________________________...

Reviews: