BAX 3345
- 10 -
JOVYTEC P 1000
Output power
cos
0,7 ind.
1000VA / 700W
Network supply
Voltage
230V
Input voltage ranges
168V - 276V (0-100% load)
140 - 159V (0-70% load)
120 - 139V (0-40% load)
Current with standard charger
4A
Current with additional charger
5,2A
Frequency
50Hz ±3Hz or 60Hz ±3Hz
Phase
Single phase
Power Factor
0,98
External fuse protection
D01/10A
Battery
(installed in battery pack inside the
ups)
Direct current link voltage
36V
Backup time
10min. at 100% load
15min. at 80% load
27min.at 50% load
Type
Maintenance free, closed lead acid batteries
Charging time
< 8 Stunden for 90% charged battery
Output
Voltage
230V Standard (208V / 220V / 240V selectable at the panel)
Frequency
Automatic adjustment by ups
Power factor
cos
0,7 ind.
Phase
Single phase
Distorsion factor
< 3% at linear load
Overload behaviour
100 to 125% for 60 seconds
125
– 150% for 10s
Crest Factor
3 : 1
Efficiency
AC to AC
88 - 98% according to the operation mode
Switch over behaviour
Power failure
0ms
Overload switching
Automatic overload switching by the ups
Noise level
At a distance of 1m
< 45dB(A)
Environment
Temperature
0°C to 40°C
+15 … +25°C (recommended)
Air humidity
0% to 95%, non condensing
Storage at
…
20°C (recommended) with Battery
-20°C to 50°C without Battery
Interfaces
RS 232-Interface
Optional:
USB-Interface
Relay card
AS/400 - Adapter
SNMP - Adapter
Supports power management and diagnosis such as BATTERY
LOW, UPS ON/OFF
Software is compatible with operating systems such as: Windows
95/98/NT/2000/XP, Novell, Unix, etc current operating systems.
Dimensions
UPS Device
Width
152mm
Depth
420mm
Heights
238mm
Weight UPS
approx. 9,4 kg
Weight UPS incl. Battery
approx. 17,4 kg
Scope of delivery
Hardware/Software
UPS unit JOVYTEC P 1000
Manual BAX 3345E
Interface cable
Software UPSMON