Wärtsilä JOVYTEC P 700VA
– 3kVA
BAX 3345
- 35 -
R E L E V A N T IN F O R M A T I O N !
It’s only allowed to install the battery cabinets within a dry room with non-
aggressive atmosphere. There has to be a distance of min. 100 mm between wall
and ventilation slots. Protect the device against direct insulation and influence of
other heat sources.
13.3.2
Battery Cabinet BM1
– BM3
These battery cabinets are fit up with flexible connection wires. At the rear of the battery cabinets are two
fuses of the battery reachable (
F1
:positive pole,
F2:
negative pole).
.
Battery Fuses
UPS Device
F1
F2
JOVYTEC P
700
35A DO2
35A DO2
JOVYTEC P
1000
35A DO2
35A DO2
JOVYTEC P
1500
35A DO2
35A DO2
JOVYTEC P
2000
35A DO2
35A DO2
JOVYTEC P
3000
35A DO2
35A DO2
Connect the battery plug of the battery connection wire with approx. 1.5 m length to the UPS.
By the connection wire you have to connect the battery cabinet with the UPS. This plug is protected
against incorrect polarity.
F1
F2