Wärtsilä JOVYTEC P 700VA 

– 3kVA 

      BAX 3345 

- 24 -

 

7.6   

OFFLINE mode 

 

The UPS unit can be operated using special settings via the display or with the software supplied in  
offline mode. This operating mode has the advantage of only using a small amount of energy. 

 

The formalism for setting to OFFLINE mode is as follows: 

 

-  The key 

FUNC

 must be pressed for 2 seconds to obtain configuration mode. 

   The first configuration parameter appears in the display. 

 

-  The key 

FUNC

 can be used to manoeuvre through the parameters. 

 

-  Select the parameter point to be altered using the key 

ENTER

, in this case: HE mode 

 

-  The key 

FUNC

 is then used to manoeuvre through the options for the selected parameter (ON/OFF). 

 

-  You have the option to select between 10% and 15%, which are the thresholds to be monitored, and if the 
voltage does not meet this criterion then the UPS switches to battery operation. 

 

-  The selected option is confirmed using the key 

ENTER

 and saved by pressing the key again. 

-  Ensure that the settings were adopted in that the display shows: High Efficiency. 
-  The UPS unit will start again automatically after restoration of the mains power and starts in the preset mode  
   after a long period of power loss where the end of the autonomy period was reached and the UPS shut down  
   once the final discharge voltage was reached. 
 
 

7.7   

Free running mode 

 

The text below explains the free running mode. The preset input frequency window of the UPS has a 
range of 45Hz - 65Hz and is referred to in the following as the input frequency range. 
The narrow input frequency range has a frequency range of 49Hz - 51Hz. This range can be set via the display 
and operates in the following ranges: 

 

I/P input frequency low = 50 x (1-0.02) = 49Hz                           I/P input frequency high = 50 x (1+0.02) = 51Hz 

 
 

7.7.1 

Free running ON 

 

If  the  input  frequency  is  49.3Hz,  this  value  is  within  the  narrow  input  frequency  range.  This  means  that  the 
output frequency is also 49.3Hz (synchronised) and the UPS unit runs in line mode. If the input frequency then 
drops below 49Hz, for example 48Hz, the input frequency is outside the narrow input frequency range but  still 
within  the broader  input frequency  window. The  output frequency  will therefore be 50Hz and the UPS unit  will 
remain in line mode. If the input frequency were 43Hz then it would be outside both the narrow and the broader 
input frequency window. The UPS unit switches to battery operation and supplies the load via the inverter with 
50Hz. 
 
 

7.7.2 

Free running OFF 

 

If  the  input  frequency  is  49.3Hz,  this  value  is  within  the  narrow  input  frequency  range.  This  means  that  the 
output frequency  is  also  49.3Hz  (synchronised)  and  the  UPS  unit  remains  in  line mode. If  the  input frequency 
then  drops  below  49Hz,  for  example  48Hz,  then  the  input  frequency  is  outside  the  specified  values  for  the 
narrow  input  frequency  range  and  the  UPS  unit  switches  to  battery  operation  and  supplies  the  load  via  the 
inverter with 50Hz. 
 
 

7.7.3 

Setting the bypass tol activation/deactivation of the bypass 

 

The UPS unit offers the option of activating and deactivating the bypass. There is also the option of setting the 
bypass network tolerance via the display (see Chapter 7.4). 
The functionality of the bypass tolerance is described below.  
If the UPS unit has a fault and the bypass is activated but the input voltage does not have the quality to supply 
the consumers then the following examples can arise: 
 

7.7.4 

Free running ON, bypass deactivated 

 

Example:

  

Input voltage for bypass:

 210 V     

Input frequency for bypass:

 52Hz     

Output voltage of UPS:

 230 V 

 

The bypass tolerance is set to +15/-20% as the bypass range window (set via the display) so the bypass 
window has the following values: 

 

Summary of Contents for JOVYTEC P 1000

Page 1: ...BAX 3345 Operating Manual W rtsil JOVYTEC P 700VA 3kVA...

Page 2: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 2 Index Date Name Revision 0 2014 06 20 Chr Fechteler 14 375 1 2014 10 29 Chr Fechteler 14 600 2 2017 08 14 D Busboom 17 262 3 4 5 6 7 8 9 10...

Page 3: ...part of the contract but simply serve as a source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this ope...

Page 4: ...G AND INDICATING ELEMENTS 21 7 1 LED AND FUNCTION KEYS 21 7 2 PARAMETERS 22 7 3 CONFIGURATION 22 7 4 TABLE OF THE ADJUSTABLE PARAMETERS 23 7 5 AUTOMATIC MANUAL BATTERY TEST 23 7 6 OFFLINE MODE 24 7 7...

Page 5: ...1 TECHNICAL DATA AUTONOMY TIMES 31 13 2 VIEWS 32 13 2 1 BATTERY CABINET B10 B12 32 13 2 2 BATTERY CABINET BM1 33 13 2 3 BATTERY CABINET BM2 33 13 2 4 BATTERY CABINET BM3 33 13 3 CONNECTION 34 13 3 1 B...

Page 6: ...discharging voltage is not reached 1 General notes The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE regulations Provisions of the loca...

Page 7: ...During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating voltag...

Page 8: ...ns that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault in th...

Page 9: ...rsion factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failur...

Page 10: ...factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms...

Page 11: ...factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms...

Page 12: ...factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms...

Page 13: ...rsion factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failur...

Page 14: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 14 238 152 5 Dimensions and views 5 1 JOVYTEC P 700 P 1500...

Page 15: ...5 Relay Card USB Interface option Connector for external Battery Load output socket Cold output socket for consumers 5 2 Rear view JOVYTEC P 700 P 1000 Electronic Stop RS232 Interface TAE Protection C...

Page 16: ...0VA 3kVA BAX 3345 16 USB Interface option 5 3 Rear view JOVYTEC P 1500 Electronic Stop RS 232 Interface TAE Protection Circuit Fan Input Fuse Main Input Plug Relay Card Connector for external Battery...

Page 17: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 17 225 360 5 4 JOVYTEC P 2000 P 3000...

Page 18: ...JOVYTEC P 2000 P 3000 Fan Fan TAE Protection Circuit RS232 Interface Electronic Stop Input Fuse Mains Input Plug Electronic Stop Relay Card USB Interface option Connector for external Battery Output...

Page 19: ...ct socket 3 Connect up the battery cabinet supplied optional for longer autonomy times via the battery connection jack 4 All connecting up work is now complete P L E A S E N O T E Only trained personn...

Page 20: ...pressing the ON OFF button and the message Switching off soon appears in the display and then the message UPS OFF The UPS unit is now shut down Please note The device fans continue to run as long as t...

Page 21: ...s the output voltage etc The formalism is as follows Press the FUNC key on a running UPS unit for 2 seconds to start the menu for the UPS unit parameters Pressing of the ENTER button selects the param...

Page 22: ...lue of the UPS in VA CPU VERSION 3 12 CPU software 7 3 Configuration Use of the function display and the function keys allows diverse settings to be made on the UPS unit The formalism is as follows In...

Page 23: ...uage selection English German French Spanish Italian German Generator mode Generator Generator mode ON OFF OFF Setting RS 232 interface COM control command Setting of RS232 interface ON OFF ON The man...

Page 24: ...1 0 02 51Hz 7 7 1 Free running ON If the input frequency is 49 3Hz this value is within the narrow input frequency range This means that the output frequency is also 49 3Hz synchronised and the UPS u...

Page 25: ...the bypass window has the following values Bypass lower limit 230 V x 1 0 2 230 V x 0 8 184 V bypass upper limit 230 V x 1 0 15 230 V x 1 15 264 5 V A 2 tolerance was selected for the input frequency...

Page 26: ...cessary The UPS switches again to normal operation after a successful battery test Overcharging over charge Continuous tone The batteries are over charged Battery charge voltage too high Contact the s...

Page 27: ...UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of power failure is possible 9 1 Connecting the UPS to the computer Th...

Page 28: ...nic STOP functionality is to be used then the bridge should be removed on the plug and an external switch opener clamped to the rear plug Actuation of the external electronic STOP switch causes the ou...

Page 29: ...mers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be restarted There is still a voltage inside and at the terminals even after the electronic STOP f...

Page 30: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 30...

Page 31: ...000 120 BM3 280 x 680 x 630 80 91 9 JOVYTEC P 1500 0 10 4 JOVYTEC P 1500 6 18 2 JOVYTEC P 1500 30 BM1 152 x 238 x 420 40 58 2 JOVYTEC P 1500 40 BM2 225 x 360 x 425 50 60 4 JOVYTEC P 1500 60 BM3 280 x...

Page 32: ...3 2 Views 13 2 1 Battery Cabinet B10 B12 Battery Cabinet Type Dimensions apporx in mm Weight without Batteries in kg A B C D E B10 470 800 1090 780 470 70 B11 470 800 1340 780 470 80 B12 910 810 1620...

Page 33: ...BM1 BM3 see Table Battery Cabinets Cabinet Socket Cable to UPS System Battery Fuses F1 F2 BATTERIE F1 F2 Air Outlet 240V ZWISCHEN KREISSPANNUNG Plastic Feet Battery Fuses F1 F2 Battery Cable to UPS Sy...

Page 34: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 34 13 3 Connection 13 3 1 Battery Cabinets B10 B11 B12 Battery Fuses Battery terminals F1 F2 X1 X2 PE 1 2 3...

Page 35: ...tery cabinets are fit up with flexible connection wires At the rear of the battery cabinets are two fuses of the battery reachable F1 positive pole F2 negative pole Battery Fuses UPS Device F1 F2 JOVY...

Page 36: ...until the battery is charged up Restoration of mains power after total discharge of the battery At the end of the bridging time the inverter switches off automatically and the consumers are no longer...

Page 37: ...t is located on the left side of the battery rack 4 Unhook the retaining bracket 5 Pull the battery pack out of the UPS unit using the pulling strap Please note that if a power failure occurs now the...

Page 38: ..._________________________________________________________________________________ ______________________________________________________________________________________ _______________________________...

Reviews: