Wärtsilä JOVYREC D600 G120/10
150254_10_BA
- 11 –
ATTENTION:
Only transport the charging rectifier in an upright position!
Never tilt or cant, always observe the centre of gravity!
Eyelet
Eyelet
The length of the cables is calculated so that an angle of 45° is given between the cable and the top edge of the
cabinet (DIN 580). The minimum load capacity of each cable must be ³ 0.5 times the weight of the cabinet (DIN
580). The weight of each charging rectifier is contained in Chapter ‘Technical Data’. One cable must be used for
each eyelet.
Proceed as follows to transport the unit by crane:
•
Check the four transport eyelets in the threaded bores on the top of the cabinet for fixed mounting.
•
Hook in the four cables.
•
Carefully lift the charging rectifier and transport the unit to its intended site.
•
Carefully lower the charging rectifier without jolting the unit.
•
Remove the cables and eyelets.
4.4.2
Transporting the Unit with a Forklift and Lowlift Truck
ATTENTION:
Prior to transport always ensure that the transport devices used for the rectifier are designed for the
respective load.
NOTE:
Transport with a forklift or lowlift truck should be avoided whenever possible, especially on construction
sites and uneven ground.
Always transport by crane when possible!
Preparation:
•
Leave the rectifier on the transport pallet.
•
Remove the base covering.
Transport with lowlift truck
Transport with forklift truck
i