![WÄRTSILÄ JOVYREC D600 G120/10 Operating Manual Download Page 29](http://html1.mh-extra.com/html/wartsila/jovyrec-d600-g120-10/jovyrec-d600-g120-10_operating-manual_3462591029.webp)
WÄRTSILÄ JOVYREC PME
BAX 5675
- 5 –
3 General technical data
The technical data specified here applies for the entire device series.
The device-specific values can be found in "Specific technical data".
Mains power connection:
1/N/PE 230V AC +15/-20% 45-66Hz
Dynamic behavior:
2 % with abrupt load changes between 90%-10%-90%
Irated (transient time < 2ms at 1% Urated).
Short-circuit behavior:
Short-circuit proof
Switching on pattern:
Softstart.
Performance factor cos
ϕ
:
0.99 for Pout = 100% Prated;
0.97 for Pout < 50% Prated;
0.95 for Pout < 25% Prated.
Output ripple without
battery:
0.3% peak-to-peak for rated output voltage 24V to220V
Output ripple without
battery frequency-weighted:
24V – 1mV as per CCITT Standard
48 and 60V – 2mV as per CCITT Standard
Characteristic curve:
IU as per DIN41773
Circuit:
Primary synchronization based on principle of pulse width control.
Clock frequency:
65 kHz
Reliable electrical
disconnection:
Up to 60V DC rated output voltage, protection from functional
low voltage with reliable electrical disconnection as per EN60950.
In excess of 60V DC rated voltage output, protection with
reliable electrical disconnection as per EN60950.
Surge category:
2 (impulse withstand voltage 2 KV - 1.2/ 50
µ
s).
Rated insulation voltage
of mains supply circuits:
a) Air clearance 424V (peak value).
b) Creepage distances in accordance with rated supply voltage
(effective value).
Noise level:
≤
59 dB at one meter distance.
Protection class:
IP20 as per DIN 40050
Cooling method:
Self-cooling with temperature controlled fans
Weight:
5,5 kg
Environmental conditions:
a) Ambient temperature: -10°C to +40°C up to +55°C with power reduction.
b) Relative humidity: 5% to 95% (at 40°C ambient temperature max. 50%
relative humidity, at 28°C ambient temperature max. 95% relative humidity).
c) Air pressure 86 KPa to 106 KPa.
d) Degree of pollution 2
Installation height:
1000 meters above NN (sea level). Power reduction at greater heights.