  Operating Manual Wärtsilä JOVYLINE 625/1200/2200 BAX 3522 E                              page 4 

1. Technical 

data 

 

1.1        Table 1: Typespecifical data 

 

UPS  (nominal power) 

625 VA 

1200 VA 

2200 VA 

Input voltage / mains voltage 

 230 V +20%  -25% 

Mains frequency 

50 / 60 Hz  

 5% (automatic switch-over) 

Output voltage 

230V  

Output frequency 

50 / 60 Hz  

 0,5% (at battery operation) 

Voltage regulation of the output 
voltage 
 

AVR increases the output voltage by 15% over input voltage, if the 
input voltage sinks within –9% up to – 25%. AVR decreases the output 
voltage by 13% compared with the input voltage, if the input voltage 
increases 9% up to +25% 

Time for switch over 

2-4 ms including detection time 

10 Base-T Cable Port 

network (UTP, RJ-45) compatible plugs 

Protection against spikes 

320 Joule, 2ms 

Overload protection 

UPS switches off after 110% overload for 60 sec. and  

                           130% overload for 3 sec. 

Short circuit protection 

UPS switches off immediately or input protection gets released 

Input protection 

Protection against overload and short circuit 

Type of battery 

Lead battery, closed maintenance-poor 

12V / 7Ah  (JOVYLINE 625)         24V / 7Ah  (JOVYLINE 1200 / 

JOVYLINE 2200)  

Charging duration battery 

4 hours up to 90% of nominal capacity 

Protection installations battery 

Automatic selftest and protection against discharging, display for 

defect batteries 

Autonomy time 

10-30 min. (in dependency on the computer load) 

Weight UPS 

6,5 kg               

13,4 kg    

15,9 kg   

Dimension (w x h x d) in mm  

97 x 320 x 135  

130 x 382 x 192 

130 x 382 x 192 

Mains input connection 

Connection acc. IEC 320 

Alarm, battery charging 

Slow bleeping tone (ca. 0,47Hz) 

Alarm, battery discharged 

Quick bleeping-tone (ca. 1,824Hz) 

Alarm, overload 

Permanent sound 

Interface RS-232 

Bi-directional com. Port 

Rules for construction 

security: VDE, TÜV, CE , 

Surrounding terms 
Placing 

 

1000m above sea level acc. to EN 62040-3 

Surrounding terms  
General 

 

humidity 0 - 95% non condensing, acc. to table DIN 40040 

0-48°C   

Decibel level acc. to ISO 7779 

< 40 dbA  

   Technical modifications be possible 

 

Summary of Contents for Jovyline 1200

Page 1: ...BAX 3522 E Operating Manual UPS Systems W rtsil JOVYLINE 625 1200 2200...

Page 2: ...before installation Pay attention to each special hint within the separate chapters to avoid later disturbances of the device right from the start In case of problems please contact our Service depart...

Page 3: ...625 1200 2200 7 4 Installation 11 5 Operation of the UPS system 12 6 Alarms 13 7 Software options 13 8 Computer interface connection 14 9 Replacing of batteries 14 10 Troubleshooting 15 _____________...

Page 4: ...itches off immediately or input protection gets released Input protection Protection against overload and short circuit Type of battery Lead battery closed maintenance poor 12V 7Ah JOVYLINE 625 24V 7A...

Page 5: ...s bracelets etc at your arms and hands which could lead to a short circuit at the poles of the battery A short circuit on the battery can produce a very high short circuit current which leads usually...

Page 6: ...ltage at the output socket is constant within separate voltage steps Please take the values out of table 1 on page 4 of this manual Production of these UPS systems is subjected to a strict quality con...

Page 7: ...in its capacity the LED lightens up You have to replace the battery 2 Battery feeds load yellow LED If the load is fed by the battery the yellow LED lightens up 3 Mains OK green LED If the input volta...

Page 8: ...ns the standardised RS 232 interface and works under the operation systems Novell Unix DOS Windows and others 6 Output sockets 7 Mains input socket with mains fuse 8 Socket for telephone modem with sp...

Page 9: ...value The load is fed with normal voltage 3 Battery feeds load yellow LED If the battery feeds the load the yellow LED lightens up 4 AVR automatic voltage regulation yellow LED The LED lightens up if...

Page 10: ...protection against voltage transients for modem network and telephone offers a completely safe internet connection 6 USV Port For communication between UPS and Computer 7 Output sockets Normal Versio...

Page 11: ...PC with the RS232 interface by the cable enclosed 4 4 Connection of external battery blocks optional Before connection of the battery block secure that the battery plug and the connection cable are c...

Page 12: ...UPS You can use the self test of the UPS to get a statement of the UPS function and battery function To start the self test you have to push the push button ON OFF during normal operation of the UPS i...

Page 13: ...o remove parts of the load or replace the UPS by a bigger one Even consumers with a high peak current absorption such as laser printer plotter or faxes lead to an overload of the UPS Therefore it s ad...

Page 14: ...nd burns 5 Place the new batteries in the same position as the old ones Connect the battery wiring to the battery again red wiring black wiring 6 Screw on the cap of the cabinet 7 Follow the instructi...

Reviews: