background image

P90L 6kVA & 10kVA Online UPS

6kVA, 10kVA Models

User & Installation Manual

www.xpcc.com

 

| © 2015 Xtreme Power Conversion Corporation. All rights reserved. (Rev 5/26/15)

Summary of Contents for P90L

Page 1: ...P90L 6kVA 10kVA Online UPS 6kVA 10kVA Models User Installation Manual www xpcc com 2015 Xtreme Power Conversion Corporation All rights reserved Rev 5 26 15...

Page 2: ...tible Power Supply Please comply with all warnings and operating instructions in this manual Save this manual and read the following instructions carefully before install ing the unit Do not operate t...

Page 3: ...cking and Inspection 7 Rear Panel View 7 System Single Line Diagram 10 Rack Tower Installation 10 UPS Electrical Installation 11 Operations 13 OperatingMode StatusDescription 13 ButtonOperation 13 LED...

Page 4: ...ion Load Protection Policy 33 Appendix A P90L BP240 User Guide 36 ImportantSafetyWarnings 36 Installation and Setup 36 Storage Maintenance 38 Appendix B P90L RAIL Installation Guide 39 PackageContents...

Page 5: ...ffectiveness is not recommended Do not use this equipment in the presence of a flammable anesthetic mixture with air oxygen or nitrous oxide Connect your UPS power module s grounding terminal to a gro...

Page 6: ...acement should be performed only by authorized service personnel using the same number and type of batteries Sealed Lead Acid Use tools with insulated handles The batteries are recyclable Do not open...

Page 7: ...ng software CD One USB cable Two sets of tower stands including feet and extensions Two Rack mounting ears Note Before installation please inspect the unit Be sure that nothing inside the package has...

Page 8: ...Xtreme Power Conversion Corporation P90L 6kVA 10kVA User s Manual Page 8 Uninterruptible Power Supply P90 BP240 Battery Pack Rear Panel Connection between P90 BP240 and P90L UPS...

Page 9: ...8 Cooling fan 9 External battery connector 10 Input circuit breaker 11 Input output terminal P90L 6K ships with default cord kit 12 Input terminal 13 Ground 14 Output terminal 15 Battery pack output c...

Page 10: ...nd BP240 battery module in tower configuration 1 For UPS only assemble two feet and one short extension together as front support Assemble rear support in the same manner 2 For UPS and Battery Module...

Page 11: ...ce with local and national code regulations 1 Make sure the mains wire and breakers in the building are rated for the correct capacity of UPS 2 Switch off the main feed before installation 3 Turn off...

Page 12: ...breaker or other protection device be tween UPS and external battery module is installed Note Set the battery module breaker in OFF position and then install the battery module Pay attention to the p...

Page 13: ...age is within voltage regulation range and ECO mode is enabled the UPS will bypass voltage to output for energy saving If the input voltage is out of the regulation range but it is still within accept...

Page 14: ...tomatically This operation is used when configuring the UPS to Rack or Tower display LED Indicators There are 4 LEDs on front panel to show the UPS working status Mode Bypass Line Battery Fault UPS po...

Page 15: ...D panel will display total load level 2 If inductive loads such as a printer are connected the in rush current should be calculated carefully to see if the capacity of the UPS is sufficient due to the...

Page 16: ...press the OFF ESC button LCD will show a prompt page of Turn Off Move the arrow to Yes by up or down button then press ON ENTER the UPS will beep once and turn off Power is still applied via bypass m...

Page 17: ...Xtreme Power Conversion Corporation P90L 6kVA 10kVA User s Manual Page 17 Uninterruptible Power Supply LCD Operation The entire LCD structure is demonstrated in diagram below...

Page 18: ...turn on the UPS to line converter ECO battery mode according to the setting and input status in reverse you could press the OFF ESC button to turn off the UPS to bypass mode or shutdown As previously...

Page 19: ...s and input status Note You could turn on the UPS by pressing ON ENTER button at the home page It s not necessary to enter into this control menu to turn on the UPS b On line mode or converter mode or...

Page 20: ...ee the change of the mute icon 4 Para Unlock Future Use This selection is for parallel protection unlock to allow for parallel unit operation It only appears when the LCD shows the warning 3F Para Pro...

Page 21: ...y Measurement Pages These pages display the measurement value of the parameters such as voltage current frequency power capacity time etc Press UP or DOWN to navigate the pages Information Pages These...

Page 22: ...that the UPS can go to Bypass mode automatically or manually Disable Bypass disabled When selected automatic bypass is ac ceptable but manual bypass is not available Manual bypass means users manuall...

Page 23: ...tting range is from 62 0Hz to 64 0Hz The default value is 52 0Hz 62 0Hz 3 Output setting only available or effective on bypass mode Interface Description 1 Volt 208 The voltage is set for 208VAC 220 T...

Page 24: ...ning time set by op tion below is met Disable Battery discharge protection function is disabled 000 999 The maximum discharge time ranging from 0 to 999mins UPS will shut down to protect battery after...

Page 25: ...modes 2 Inv Adjust the inverter output voltage the adjustable range is from 0V to 6 4V the default value is 0V It is only available in line battery converter mode 3 Chg Adjust the Charger output volt...

Page 26: ...the UPS system does not operate correctly please solve the problem by referring to the table below Alarm type LCD display Possible cause Remedy Warning 01 Batt Open The battery connection is loose Th...

Page 27: ...Protect Future Use Parallel cable is still not connected when restart after the parallel system is faulty because of parallel communication failure When this warning appears the UPS can not start up i...

Page 28: ...Fault 21 Batt SCR Short The internal battery SCR has failed shorted Contact the dealer for repair Fault 24 Inv Rly Short The internal inverter relay is stuck in the shorted position or the SCR of STS...

Page 29: ...e storing charge the UPS batteries for at least 7 hours Store the UPS covered and upright in a cool dry loca tion During storage recharge the battery in accordance with the following table Storage Tem...

Page 30: ...ection Terminal block with 3 ft L6 30R Terminal block ENVIRONMENT Operating temperature 32 104 F 0 40 C Audible noise 58dBA 60dBA Altitude 11 500 ft above sea level OPTIONAL BATTERY PACKS Model number...

Page 31: ...will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Autho...

Page 32: ...a the equipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subje...

Page 33: ...the XPC Limited Warranty against certain losses caused by a Power Disturbance for properly connected electronic equipment referred to as the Connected Equipment subject to certain terms and conditions...

Page 34: ...e Load Protection Policy The following damage is not covered by this Policy 1 Restoration of lost data and reinstallation of software 2 Damage from a cause other than AC power line transients except f...

Page 35: ...issue payment to the Purchaser for either the cost of repair of the Connected Equipment or the Fair Market Value of the damaged Connected Equipment up to the dollar limits stated above XPC reserves t...

Page 36: ...battery will discharge naturally if the system is unused for a period of time It should be recharged every 2 3 months if unused If this is not done then the warranty will be null and void During norm...

Page 37: ...Ear x 2 screw x 8 Extended stand Selecting Installation Position 1 It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the battery box...

Page 38: ...If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer Storage Before storing charge the unit 4 hour...

Page 39: ...r Supply Appendix B P90L RAIL Installation Guide Package Contents Right rail slider x 1 Left rail slider x 1 Nut M6 x 6 Screw M6 x 14 Assembly Steps Step 1 Use 4 screws to mount right and left rail sl...

Page 40: ...on P90L 6kVA 10kVA User s Manual Page 40 Uninterruptible Power Supply Step 2 Use 4 screws to mount rail sliders in back See chart below Step 3 According to UPS height put nuts on proper location Step...

Page 41: ...Xtreme Power Conversion Corporation P90L 6kVA 10kVA User s Manual Page 41 Uninterruptible Power Supply Step 5 Fix the UPS in position with screws Step 6 Assembly complete...

Page 42: ...ks smoke or gas Make sure the unit is installed within a proper environment as specified a Keep it in the place of 0 40 C and 30 90 non condensing humidity b Keep away from direct sunlight c Keep away...

Page 43: ...Supply Rear Panel Explanation 6kVA 10kVA A RJ 45 Communication port B Input Output Terminal Block C For UPS Input 6kVA only D Maintenance Bypass Switch E Air Ventilation Openings 6kVA only F Thermal b...

Page 44: ...Position It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the unit and extend the life of the unit Please follow the advice below Ke...

Page 45: ...B P90L EBP240 2 1 6 3 4 5 1 Hardwired input from Utility Input 2 L6 30P cord from UPS input connectes to L6 30R on P90L ISO6MB UPS Input 3 L6 30R cord from UPS connects with L6 30P on P90L ISO6MB UPS...

Page 46: ...ed input from utility 2 Hardwired input cord with ring terminals connects to utility input terminals on P90L ISO10MB terminal block 3 Hardwired output cord with ring terminals connets to UPS output te...

Page 47: ...erminals as Utility Input G1 Input Ground L2 N2 Connect to UPS Output Terminal G2 Connect to UPS Output Ground Terminal L11 L12 N11 L22 N22 the Output Terminals of the Unit G3 The Output Ground Termin...

Page 48: ...internally for 6kVA only 10kVA jumpers are to be made in the field shown below Contact Technical Support for additional voltage configurations if needed P90L ISO6MB Internal Jumper P90L ISO10MB Intern...

Page 49: ...age Unit w o Bypass Switch 160 280Vac 1 Unit w Bypass Switch INV 160 280Vac 1 184 280Vac 1 BYPASS Current N A 30A max 50A max Frequency N A 50Hz 60Hz 5Hz Output Terminal Voltage N A 184 280Vac 1 Curre...

Reviews: