Fig 14-5
Typical signal overview (Generating set)
14.2
Functions
14.2.1
Start
14.2.1.1
Start blocking
Starting is inhibited by the following functions:
●
Turning device engaged
●
Pre-lubricating pressure low (override if black-out input is high and within last 30 minutes
after the pressure has dropped below the set point of 0.8 bar)
●
Stop signal to engine activated (safety shut-down, emergency stop, normal stop)
●
External start block active
DBAE248994
14-7
14. Automation System