Object
Manufacturer
Type-model / Technical data
Procedure setting or checking Cascade parameters
Warmhaus
Viwa 90,115,125,150
0
Attention:
This procedure must be applied by authorised persons and valid for only condensing
boiler.
Attention:
The parameters as indicated DO NOT CHANGE should not be adjusted / touched by any
official document suppiled by Warmhaus R&D.
1
Keep pressing the CHIMNEY SWEEP and INFO button simultaneously until SET Par01 shown on the
screen.
Release the buttons when SET Par01 shown on the screen.
Par 1 to Par 49 - INSTALLER MENU
2
The screen will appear SET - Parameter = 01 - Value = 01
Attention:
do not change this parameter
3
To toggle switch CASCADE parameter list;
Keep pressing CHIMNEY SWEEP and INFO button simultaneously until on the screen shown "
cd
"
Release the buttons when "
cd
" symbol shown on the screen.
4
On the screen CODE symbol shown as "
cd
" from this moment the KEY CODE must be entered by
button combinations.
5
The CODE is button combination push the buttons given bellow sequence for CASCADE MENU ;
HI > LO > INFO > CHIMNEY SWEEP > INFO
6
From this moment toggle;
INFO ( + ) to increase
OR
CHIMNEY SWEEP ( -) to decrease
any parameter aimed to be changed.
7
Ones you reach the parameter aimed to be changed, Change the parameter VALUE by using the (+)
or (-) buttons.
7
Example; Push INFO to reach Par A1 ones reached Par A1 on bottom corner, value of paramater A1
can be changed by button (+) or (-) while CASCADE menu activated.
When parameter VALUE changed wait for 2-3 Second then value will be saved automatically.
8
PAR A0 = Default = 0 Cascade strategy selection
Value band; 0= Fixed set. / 1= Dynamic set
9
PAR A1 = Default = 2 Number of boiler to be Cascaded
Value band; 0 – 8
This Parameter has to be changed on master boiler only to enter how many boiler
cascaded on the installation via Modbus.
10
PAR A2 = Default = 0 Reset for Cascad burner working hours
Value band; 0 / 1 = reset
With this parameter, the total time of cascade burner operation can be reset.
6.10. SET CASCADE PARAMETERS MENU