background image

13

warmhaus.co.uk

Error

Code

Description of the Error

Malfunction

Probable Cause

Solution(s)

E 21

Delta Temperature Central 

Heating flow and Return > TSP 

82 value °C

Boiler does not work, E21 error 

code flashing on the screen

> Lack of water on the system

> Pump blockage

> Pump failure

> Pump harness

> Installation blockage

1) RESET boiler at first check if problem removed

2) Check boiler central heating valves are open if they are closed 

open all

3) Check all radiator valves are open if they are closed. Minimum  

3 meters of radiator must be open

4) RESET boiler and check if problem resolved

5) Call for authorised service

E 28

Maximum allowed consecutive 

lock-out reset reached

Usable RESET number 

reached.

Too many consecutive lock-out 

failures (followed by reset) due 

to other possible causes

1) Turn OFF the power of the appliance. Reset will be allowed 

after turning ON the power.

2) Check the root cause of Error to solve

3) If fault still persists call for authorised service

E 37

Low voltage anomaly

Boiler does not work, E37 error 

code flashing on the screen

Low voltage < 165 VAC +/- 5%

on the supply network during 

normal operation OR < 182 

VAC +/- 5% during Au-TO 

calibration mode 

1) Call for Electrical supply network provider

2) Error will remove if supply voltage > 170 VAC +/- 5%

3) If this failure is observed during calibration calibration can not 

be complete unless supply voltage > 188 VAC +/- 5%

E 40

Wrong network frequency

survey

Boiler does not work, E40 

error code flashing on the 

screen

Wrong frequency of the 

electric supply network. Value 

out of tolerance, 50 Hz +/- 5% 

1) Call for Electrical supply network provider

2) Error will remove if supply frquency 50 Hz +/- 5%

E 41

Loss of flame more than 6 

successive times

Boiler does not work, E41 error 

code flashing on the screen

> Too many domestic hot 

water

request in short period ( 1 

min )

> Low gas pressure

1) Call for authorised service at first

E 42

Buttons anomaly

Boiler does not work, E42 error 

code flashing on the screen

Wrong parameters settled on 

TsP menu

1) Call For authorised service.

E 43

Opentherm Communication

error

Boiler does not work, E43 

error code flashing on the 

screen after 1 minute of 

communication error

Opentherm line disconnected

1) Remove energy from boiler and re energize E43 will be 

removed and boiler & buttons will get back to funcitional

2) Replace the room unit batteries with the fresh ones and reset 

from room unit

3) Check cabling between boiler and room unit and re connect 

if any disconnection, if connection set up succesfully then 

connection symbol will be activated on the screen

4) Call for authorised service to re connect openterm connection

E 44

Cumulated intermittent

ignition without reaching

burner ignition.

Boiler does not work, E44 

error code flashing on the 

screen

> Intermittent contacts on 

harness

> Hammer effect on water net

> Too many requests in short

time

1) Reset & Restart boiler

2) Call for authorised service

E 62

Calibration request

Boiler does not work, E62 error 

code flashing on the screen

> Calibration not done

> Replacing board but not 

service

key from the old board (PCB)

> Service key damaged or

disconnected

> Updating Software

1) Call For authorised service

E 72

Delta T heating at ignition not 

occurred

Boiler does not work, E72 error 

code flashing on the screen

> FLOW OR RETURN Sensor 

not in

position

1) Call for authorised service at first

2) Check RETURN and FLOW sensor on position.

E 74

Second CH temperature Probe 

faulty

Boiler does not work, E74 error 

code flashing on the screen

> FLOW and LIMIT Sensor 

(double NTC ) faulty

1) Reset & Restart boiler

2) Call for authorised service.

E 77

Absolute current values 

reached

Boiler does not work, E77 error 

code flashing on the screen

> Gas inlet pressure

> Aging or rust on the 

electrode

> Recirculation of exhaust gas 

into fresh air

> Blockage in flue or wrong 

flue

> Electrode position

> Cabling disconnections

> Combustion calibration

> Electronic board

> Gas valve failure

1) Call for authorised service

E 78

Max regulation current value 

reached

Boiler does not work, E78 error 

code flashing on the screen

> Gas inlet pressure

> Aging or rust on the 

electrode

> Recirculation of exhaust gas 

into fresh air

> Blockage in flue or wrong 

flue

> Electrode position

> Cabling disconnections

> Combustion calibration

> Electronic board

> Gas valve failure

1) Call for authorised service

Summary of Contents for EWA 2525C

Page 1: ...CONDENSING COMBI BOILERS USER MANUAL EWA 2525C EWA 2530C...

Page 2: ...ith limited mental and sensory capabilities or by persons who do not have enough experience and or knowledge unless they are supervised by a person who is responsible for their safety or they have bee...

Page 3: ...of On Off Stand by and Summer Winter Modes 8 2 1 3 On Off Stand by Positions 8 2 1 4 Operation in Winter Mode 8 2 1 5 Operation in Summer Mode 9 2 1 6 Shutting off the Boiler 9 2 2 USE WITH ROOM THERM...

Page 4: ...le The maintenance and repairs as the result of failure of the product within the warranty period due to material production and installation errors shall be performed as free of charge without claimi...

Page 5: ...mbar G25 DE II 2L3P Natural Gas 25 mbar G25 NL II 2L3B P Natural Gas 25 mbar G25 NL II 2ELL3B P Natural Gas 20 mbar G25 DE I 3 Buthane Gas 28 30 mbar 37 mbar G30 BE CH CY CZ ES FR GB GR IE IT LT PT S...

Page 6: ...ly at the gas meter or an appropriate emergency control valve Immediately evacuate the place Call the National Gas Emergency Service 0800111999 or in Ireland 1850 20 50 50 Do not make any intervention...

Page 7: ...klet are strictly followed for safe and economical operation of the boiler Important Notes This appliance must not be operated without the casing correctly fitted and forming an adequate seal If the b...

Page 8: ...the first time screen displays nG letter and then a number for instance 24 indicating kW power of the device and screenlight is closed Now combi is at STANDBY position The temperature value when elect...

Page 9: ...60 C with the Domestic Hot Water temperature adjustment button 4 Screen light will be open during adjustment tap symbol and Domestic Hot Water temperature value will flash You can adjust the hot tap...

Page 10: ...n Device installation shall only be performed by the Warmhaus Authorised Service The dual cable required for installation is supplied by the dealer consumer Maintenance and Service Life Warmhaus room...

Page 11: ...r systems to operate at high temperatures as standard P24 Child Protection This feature is disabled as default factory setting 0 Child Protection key lock is enabled when parameter is adjusted to 1 Ke...

Page 12: ...stion or electrode Condensate Syphon blocked Electronic board 1 Call for authorised service E 09 No water circulation in the system Boiler does not work E09 error code flashing on the screen Lack of w...

Page 13: ...mmunication error Boiler does not work E43 error code flashing on the screen after 1 minute of communication error Opentherm line disconnected 1 Remove energy from boiler and re energize E43 will be r...

Page 14: ...disconnections Gas valve failure 1 Call for authorised service E 88 Fault of electronic gas valve managing circuit Boiler does not work E88 error code flashing on the screen Cabling disconnections Ga...

Page 15: ...ectrode Electrode position Combustion calibration 1 Call for authorised service E 96 Flue or air suction way blockage Boiler does not work E96 error code flashing on the screen Blockage in flue Blocka...

Page 16: ...and also you can acquire approximately 6 power saving with every degree of temperature decrease Ventilation Do not leave windows slightly open for ventilating room rooms In such case continuous heat l...

Page 17: ...oduct information listed elsewhere may result in different test conditions Only the data that is contained in this product information is applicable and valid Electricity Fuel HANDING OVER After compl...

Page 18: ...fuel consumption AFC GJ 11 18 11 18 Condensing boiler Yes Yes Yes Yes Low temperature boiler Yes Yes Yes Yes Combi Boilernation boiler Yes Yes Yes Yes B1 Boiler No No No No Room boiler with combi boil...

Page 19: ...19 warmhaus co uk...

Page 20: ...act Cadent s Plant Protection team Cadent provide first line support for our assets Gas Emergencies If you smell gas or have accidentally hit the NTS pipeline please call us urgently 0800 111 999 Elec...

Reviews: