Product Manual WDC400
Wallgate
2014
24
|Revision 3.0
5.6.4
System Test function
The control unit includes a
System Test
function to test the inputs (pushbuttons or infra red
sensors) and the outputs (water valves). This is useful for fault finding if any of the valves fail
to operate. You can also use this function to make sure that the pushbuttons and valves
have been connected to the correct sockets on the control unit.
To start the
System Test
function:
1.
Press and hold down the
Menu
and keys for five seconds.
The firmware version appears.
2.
Press the
↓
key once.
The
System Settings Management
menu item appears.
3.
Press the key once.
The words
System Test Disabled
appear in the display.
4.
Press the key once.
5.
Press the
↓
key once to choose Enable.
6.
Press the key once to save the setting.
7.
Operate each pushbutton and sensor connected to the control unit, one at a time.
The display in the control unit momentarily displays the letter assigned to the input. For
a list of letters assigned to the inputs, refer to the front panel of the control unit. The
applicable valve connected to the related output also opens momentarily.
As the input letter is displayed, make sure that the correct valve opens.
To check the lighting connections, do the following:
8.
Operate the lighting switches one by one and make sure that the correct display
code appears. For a list of display codes, refer to Table 2 on page 25 and Table 1 on
page 16.
9.
To stop the
System Test
, switch off the control unit.
Or
10.
Press and hold down the
Menu
and keys for 5 seconds.