Maintenance
Inspection of basic functions (3)
After the first 100 l, or after the first season of use
or after maintenance, you must
always check that the heater’s burner functions properly.
•
Start up the heater and let it run for 15 minutes.
•
Check the observation window and see if the thermal radiator is glowing red,
and whether the flame is stable.
• The burner should have several separate flames with smooth sides. The flame
may be either entirely blue or blue-and-yellow.
• If the flame is stable and the thermal radiator is red, the burner and the heater
are working normally.
• If you cannot distinguish separate flames or the flames are entirely yellow and
unstable, there are air leaks in the burner. In this case, reopen the heater and
check all the burner connections for air leaks.
• If the burner flame gradually becomes unstable while the heater is in use, the
burner probably needs cleaning.
Fuel pump
Components of the fuel system
Fuel feed pipe
Intake hose bayonet coupling
Fuel intake hose
Sinter bronze filter
Protective spiral
en
26CC / 40CC
D80151
- 58 -
490525C