Touch Panel Standard Line
Properties 51
762-4xxx TP 600
Manual
Version 1.3.0
Figure 21: Dependence between Storage Temperature and Relative Humidity
4.9.5
Power Supply
Table 23: Technical Data
‒ Power Supply
PIO1
Operating Voltage
SELV (Safety Extra Low Voltage) –
voltage source that meets the
requirements of a LPS (Limited Power
Source) as per EN 60950-1
24 VDC (−25 ... +30 %)
with reverse voltage protection
Max. current and power consumption
at 24 V, without external USB devices
4,3“:
240 mA,
5,6 W
5,7“:
265 mA,
6,4 W
7,0“:
346 mA,
8,3 W
10,1“: 480 mA, 11,5 W
Max. current consumption across the
entire voltage range,
without/with external USB devices
4,3“:
310 mA/575 mA
5,7“:
360 mA/640 mA
7,0“:
460 mA/760 mA
10,1“:
640 mA/940 mA
Max. power consumption across the
entire voltage range,
without/with external USB devices
4,3“:
6,0 W /11,2 W
5,7“:
7,0 W/12,0 W
7,0“:
8,8 W/13,9 W
10,1“:
11,8 W/17,0 W