Process Image
WAGO-I/O-SYSTEM 750
750-632 Proportional Valve Module
Manual
Version 1.3.0, valid from FW/HW-Version 01/01
Table 47: Locking the Bits M_UP and M_DOWN
JOGPOS_ACK
JOGNEG_ACK
Action
0
0
No change of value
0
1
Falling ramp
1
0
Rising ramp
1
1
No change of value
Table 48: Status Byte S1
Status Byte S1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
JOGPOS_
ACK
JOGNEG_
ACK
DITHER_S
T
DI1
DI2
0
ON_
TARGET
READY
Key
JOGPOS_
ACK
JOGPOS_ACK
Acknowledgment bit for JOGPOS
JOGNEG_ACK
JOGNEG_ACK
Acknowledgment bit for JOGNEG
DITHER_ST
DITHER_ST Status of dither function
0:
Dithering OFF
1:
Dithering ON
Dither amplitude according to parameterization
DI1
Function for the configuration of 1 valve:
V1_Status1
V1_Status1.DI1
Status digital input DI1:
0: Uin < 5 V
1: Uin > 15 V
DI2
Function for the configuration of 1 valve:
V1_Status1.DI2
Status digital input DI2
0: Uin < 5 V
1: Uin > 15 V
ON_TARGET
0: Actual value is not in the range “Setpoint value +/- ON_TARGET_WINDOW”.
1: Actual value is in the range “Setpoint value +/- ON_TARGET_WINDOW”.*
READY
0: Output stage deactivated, e.g. due to an error
1: Output stage activated
* Applies to software version 03 or higher
Table 49: Status Byte S2
Status Byte S2
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
JOGPOS_
ACK
JOGNEG_
ACK
DITHER_S
T
reserved
reserved
reserved
ON_TARG
ET
READY
Key
JOGPOS_
ACK
JOGPOS_ACK
Acknowledgment bit for JOGPOS
JOGNEG_ACK
JOGNEG_ACK
Acknowledgment bit for JOGNEG
DITHER_ST
DITHER_ST Status of dither function
0:
Dithering OFF
1:
Dithering ON
Dither amplitude according to parameterization
Bit 4 … Bit 2
0: reserved
ON_TARGET
0: Actual value is not in the range “Setpoint value +/- ON_TARGET_WINDOW”.
1: Actual value is in the range “Setpoint value +/- ON_TARGET_WINDOW”.*
READY
0: Output stage deactivated, e.g. due to an error
1: Output stage activated
* Applies to software version 03 or higher