WAGO-I/O-SYSTEM 750
Function Description
47
750-632 Proportional Valve Module
Manual
Version 1.3.0, valid from FW/HW-Version 01/01
Table 31: Approach End Stop Value
No. Event
Description/Behavior
1
Set
SPL_EN
to “0”
“JOG mode” is activated.
Present current level is maintained.
2
Set
JOG_POS
to “1”
Set
JOG_POS
to “0”
Present current level is increased.
Present current level is maintained.
3
Set
JOG_POS
to “1”
Present current level is increased.
4
Set
DI
to “1”.
Rising ramp stops. Actual value drops until the
end stop value is reached. The actual value is
then frozen.
5
Set
DI
to “0”.
Present current level is maintained.
6
Set
JOG_POS
to “0”
Present current level is maintained.
7
Set
JOG_NEG
to “1”
Set
JOG_NEG
to “0”
Present current level is reduced
Present current level is maintained.
8
Set
JOG_POS
to “1”
Present current level is increased.
9
Set
DI
to “1”.
Rising ramp stops. Actual value drops until the
end stop value is reached. The actual value is
then frozen.
10
Set
JOG_POS
to “0”
Present current level is maintained.
11
Set
JOG_POS
to “1”
Set
JOG_POS
to “0”
Present current level is increased
(even if the DI is still active).
Present current level is maintained.
12
Set
DI
to “0”.
Present current level is maintained.