
WAGO-I/O-SYSTEM 750
Function Description
39
750-632 Proportional Valve Module
Manual
Version 1.3.0, valid from FW/HW-Version 01/01
5.3.3
“Tip Mode”
The “Tip mode” function is a variant of the “Jog mode” function. In this case, the
change in current is not controlled by level. At a rising edge, the current is
increased or decreased for a parameterizable time period.
In this operating mode, the I/O module changes the control value by a fixed
amount, independent from the duration of the applied signal. For example, a drive
runs for a previously defined time in a fixed direction, and then stops, regardless
of how long a corresponding button is activated.
Figure 12: Tip Mode
Table 25: Tip Mode
No. Event
Description/Behavior
1
Set
SPL_EN
to “0”
“Jog mode” is activated.
2
Present current level is maintained.
3
Set
JOG_POS
to “1”
Present current level is increased for the time
T
parameterized in
PH_TIP_TIME.
4
Set
JOG_NEG
to “1”
Present current level is reduced for the time
T
parameterized in
PH_TIP_TIME.
5
Set
JOG_POS
to “1”
Set
JOG_NEG
to “1”
Present current level is maintained.
Do not exceed minimum or maximum values!
As soon as the control value ±100 % has been achieved, no other change occurs.