WAGO-I/O-SYSTEM 750 XTR
Appendix 299
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
Table 114: Parameter 37
Parameter 37 – Interval Autom. Reset Min/Max Values Phase 1
Function
Data Type Access
Factory Setting
Time constant for automatic deletion of minimum
and maximum values of phase 1, resolution 200
ms,
activation via register 32, bit 8 required
UINT
R/W
0x000A (2 s)
Table 115: Parameter 38
Parameter 38 – Interval Autom. Reset Min/Max Values Phase 2
Function
Data Type Access
Factory Setting
Time constant for automatic deletion of minimum
and maximum values of phase 2, resolution 200
ms,
activation via register 32, bit 9 required
UINT
R/W
0x000A (2 s)
Table 116: Parameter 39
Parameter 39 – Interval Autom. Reset Min/Max Values Phase 3
Function
Data Type Access
Factory Setting
Time constant for automatic deletion of minimum
and maximum values of phase 3, resolution 200
ms,
activation via register 32, bit 10 required
UINT
R/W
0x000A (2 s)
Table 117: Parameter 40 (Supported by Firmware Versions 05 and above)
Parameter 40 – NOLOAD Threshold, Effective Power
Function
Data Type Access
Factory Setting
NOLOAD threshold for effective power
UINT
R/W
0x0000 (disabled)
0:
The NOLOAD threshold is disabled (factory setting)
1 … 30000: Power threshold as NOLOAD limit value.
Resolution: 0.001 % / LSB (0.001 % to 30.000 %)
The threshold is specified as a % of the full scale of the power
750-495/040-000
P
Fullscale
= 1,014.91 W
750-495/040-001
P
Fullscale
= 4,465.63 W
750-495/040-002 RT500
P
Fullscale
= 2,223,038.77 W
750-495/040-002 RT2000
P
Fullscale
= 2,224,048.33 W
750-495/040-002 RC70
P
Fullscale
= 1,977,032.33 W
750-495/040-002 RC125
P
Fullscale
= 1,973,632.66 W
750-495/040-002 RC175
P
Fullscale
= 1,970,064.91 W
750-495/040-002 with user-defined RC: See the following section “Calculation of
the NoLoad Limit for User-Defined Rogowski Coils.”