wc_tx003871gb_FM10.fm
160
Machines with Aftertreatment Exhaust System
15.5
Monitoring DEF Quality
The quality of Diesel Exhaust Fluid (DEF) is monitored by the genset controller.
When the DEF quality begins to deteriorate (or something other than DEF is put
into the DEF tank, or the sensor is disconnected/malfunctioning), the genset
controller displays messages alerting the operator as to the condition of the DEF
quality. See table below.
DEF WARNING
wc_gr012297
DEF Quality
/malfunction
Controller Message
Controller / Machine Response
No
issues
detected
No message
Normal screen / normal operation
Issue
detected
DEF WARNING
■
Normal operation.
■
LED flashes.
The SEVERE INDUCMT timer starts.
90 minutes after
issue is detected
DEF INDUCEMENT
■
Main circuit breaker trips.
■
Machine runs for 10 minutes, then shuts down. LED on
solid.
The machine may be restarted, but will only run for 10
minutes before the genset controller shuts down the
machine. Only the convenience receptacles are available.
165 minutes after
issue detected
DEF PRESVR INDUCMT
Same as above.
180 minutes after
issue detected
DEF SEVERE INDUCMT
■
After 180 minutes of run time with a DEF quality issue,
the engine shuts itself down. This is the first of four
shutdowns allowed by the engine.
Note: The genset controller’s 10-minute run time
limitation is still active within the 180-minute engine run
time limit. Thus, up to seventeen restarts by the genset
controller are possible within the 180-minute engine
controlled run time.
■
The engine may be restarted, but the run time is
lessened to 30 minutes. At the 30-minute mark, the
engine shuts itself down. This is the second of four
allowed shutdowns. The genset controller’s 10-minute
run time limitation is still active. Thus, up to three
restarts by the genset controller are possible within the
30-minute engine controlled run time limit. On the fourth
shutdown, the engine controller will lock out the engine.
The engine can only be unlocked by a Cummins service
technician.
Summary of Contents for G 240
Page 1: ...5000186930 09 0215 5 0 0 0 1 8 6 9 3 0 Operator s Manual Mobile Generator G 230 G 240 EN...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes...
Page 178: ...wc_tx003849gb_FM10 fm 178 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770051...
Page 179: ...wc_tx003849gb_FM10 fm 179 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770052...
Page 180: ...wc_tx003849gb_FM10 fm 180 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770048...
Page 184: ...wc_tx003663gb_FM10 fm 184 Engine Maintenance T4i Cummins QSB6 7 770016...
Page 211: ...wc_tx003111gb_FM10 fm 211 User s Information for Transport Canada Fuel Tank...
Page 212: ...wc_tx003111gb_FM10 fm 212 User s Information for Transport Canada Fuel Tank...
Page 252: ......
Page 253: ......